8-SAFETY DEVICES AND ALARMS
BLOCKED PRODUCT
The following may cause the product to be mechanically blocked:
• structure overheating (“
A03
”).
• smoke overheating (“
A04
”).
• During product operation, uncontrolled air has entered the combustion chamber or there is an obstruction in the flue (“
A05
”).
• Boiler overheating (“
A18
”)
SOLUTIONS:
if “
A03
” appears: the structure is too hot because the product has been used for too long at the maximum power or due to poor ventilation
or because the air fans are faulty.
When the product is sufficiently cold, press button
B
on the control panel to delete alarm
A03
. Once the alarm is deleted, the product can
be switched back on.
If the “
A04
” alarm appears, the product switches off automatically. Let it cool for a few minutes and then switch t back on.
If the “
A05
” alarm appears: the door has been left open for too long or a significant amount of air has entered (ex. missing smoke fan
inspection cap). If these causes are excluded, check and if necessary clean the smoke duct and chimney.
If the “
A18
” alarm appears: the stove switches off when the boiler overheats. This may be caused by the lack of water circulation (blocked
or failed pump). Check correct pump operation
The product can be switched on again only after having eliminated the cause permanently.