8-LCD REMOTE CONTROL
TIMER MODE (TIMER)
Select this operating mode to switch the product on and off automatically, according to 6 customised time bands (P1 – P6). The following
can be set for each time band:
• Start-up time.
• Shutdown time.
• Desired room temperature during that time band.
• Days of the week when the time band is to be activated.
When the appliance is switched on (manually via button A or automatically via a time band), it operates in the automatic mode, described
above. A time band appears automatically when it is active (P1 in figure 3) and the desired temperature is changed to the value set in the
time band. However, the user can always modify this value as desired and in real time.
Refer to “Timer Settings” to learn how to set the time bands.
ECO MODE (ECO)
This mode is activated/deactivated by pressing key B for 5” on the remote control while it is switched on.
ECO is an automatic mode with the only difference that if the set temperature is reached and remains so for the subsequent 20 minutes
(despite flame modulation), the product is switched off and remains on stand by until the room temperature drops 2 degrees below the
desired temperature (and in any case for at least 5 minutes from the last shutdown). The product is then switched on again,Figure 4.
If the room is not sufficiently insulated, flame modulation does not allow the set temperature to be met for 20 consecutive minutes and
the product will not go off.
NOTE: It is recommended to use the ECO mode only in well-insulated rooms in order to prevent start-up and shutdown from
occurring within short periods of time.
The remote control remains on even when the product is off when in ECO mode, in order to indicate that this shutdown is only temporary.
Obviously, if the product is switched off from key A, ECO mode is exited and the product remains off.
Up to 6 automatic start-up and shutdown time bands (E1 – E6) can also be set in ECO mode, which are independent from those of TIMER
mode (P1 – P6). If they have been activated, TIMER-ECO appears on the display (figure 5) permanently, even if the remote control is
switched off.
Refer to “Timer Settings” to learn how to set the time bands.
NOTE: If the remote control is switched off due to TIMER, ECO cannot be restarted until the user intervenes (key A) or when the
next valid time band is started. Combined use of TIMER and ECO modes requires a good knowledge of the product operating
logic.
FIGURE 3