Table 9 Supply Fan Motor Data
Supply Power Wiring
1.
Units require three-phase power supply.
2.
Allowable voltage tolerances:
a. 60 Hertz
Nameplate 208V: Min.187V, Max. 229V
Nameplate 230V: Min.207V, Max. 253V
Nameplate 460V: Min.414V, Max. 506V
Nameplate 575V: Min.518V, Max. 632V
b. 50 Hertz
Nameplate 400V: Min. 342V, Max. 418V
3.
Power lead wire sizing:
a. For units with cooling capability (all concurrent
loads) with or without hot water heating and circuits
with motor loads only:
MCA = 1.25 (largest motor RLA or FLA) + other
loads + 2 amps.
b. For units with cooling capability and non concurrent
electric heat capability:
In the cooling mode, the loads will be composed of
supply fan motor and compressors. In heating mode,
the loads will be composed of supply fan motor and
electric heater. The MCA is calculated for unit run-
ning in either mode; the highest value obtained is used
for the MCA.
(1) For unit in cooling mode:
MCA = 1.25 (largest RLA or FLA) + other loads +
2 amps.
(2) For unit in heating mode:
MCA = 1.25 (electric heat FLA + Fan FLA) + 2
amps.
4.
Size wires in accordance with Table 310-16 or 310-19 of
the National Electrical Code.
5.
Wires should be sized for a maximum of 3% voltage
drop.
Lug Sizes For Single Disconnect or
Power Block
Horsepower
TYPE
208/60/3
230/60/3
400/50/3
a
a.
460/60/3 motors are used. Derate nameplate horsepower to 0.83 to obtain actual horsepower.
460/60/3
575/60/3
FLA
FLA
FLA
FLA
FLA
3
High Efficiency
9.9
9.0
4.5
4.5
3.4
Premium Efficiency
9.3
8.2
4.1
4.1
3.1
5
High Efficiency
14.8
14.0
7.0
7.0
5.3
Premium Efficiency
15.7
13.6
6.8
6.8
5.2
7.5
High Efficiency
22.3
21.6
10.8
10.8
8.2
Premium Efficiency
22.3
20.0
10.0
10.0
7.4
10
High Efficiency
29.7
28.0
14.0
14.0
11.0
Premium Efficiency
29.0
25.8
12.9
12.9
10.3
15
High Efficiency
44.4
40.6
20.3
20.3
16.2
Premium Efficiency
43.4
37.8
18.9
18.9
14.1
20
High Efficiency
57.0
50.0
25.0
25.0
20.0
Premium Efficiency
57.0
49.0
24.5
24.5
18.9
25
High Efficiency
69.8
62.0
31.0
31.0
24.3
Premium Efficiency
70.5
61.0
30.5
30.5
24.2
Table 10. Single Disconnect
UNIT
VOLTAGE
SIZE (AMPS)
018-028
208/230
225
018-028
400/460
100
018-028
575
100
035-040
208/230
225
035-040
400/460
150
035
575
100
040
575
150
Table 11. Lug Sizes For Single Disconnect
DISCONNECT SIZE
LUG SIZE
100
#6-2/0
150
#2-3/0
225
#3-300 MCM
Table 12. Lug Sizes For Power Block
UNIT
VOLTAGE
LUG SIZE
018-040
ALL
#6-400 MCM
Содержание SWT C Series
Страница 23: ...IM709 23 Typical Wiring Schematics Figure 19 Power Schematic...
Страница 24: ...24 IM709 Figure 20 Input Schematic Discharge Air Control DAC...
Страница 25: ...IM709 25 Figure 21 Input Schematic Zone or Space Comfort Control SCC...
Страница 26: ...26 IM709 Figure 22 Output Schematic Actuator Control...
Страница 27: ...IM709 27 Figure 23 Output Schematic Auxiliary Fan Start Stop Control...
Страница 28: ...28 IM709 Figure 24 Output Schematic Actuator Control...
Страница 29: ...IM709 29 Figure 25 Output Schematic Compressor Control 4 Compressors 4 5 or 6 Stage...
Страница 44: ...13600 Industrial Park Boulevard Minneapolis MN 55441 USA 763 553 5330...