37
Variable air volume (VAV) start-up
Enter the duct static pressure setpoint value and parameters
through the keyboard:
Air/Water Flow
Duct static pressure
Ducts SPT
When the appropriate number of VAV terminal boxes are
opened by setting down there respective thermostats, the
vanes should go to the maximum airflow. Upon closing
enough VAV boxes by setting their respective thermostats
up, the inlet vanes should go to the minimum airflow posi-
tion.
Rpm changes
All units are provided with fixed pitch sheaves selected for
the specified operating conditions. If a new fan rpm selection
is required a new sheave selection will need to be field
installed. Adjust belt tension as described below.
Drive sheave alignment and belt tension
Drive sheave alignment should be checked using the four-
point method shown in Figure 27. When measuring from the
straight edge to the belt, the dimensions A, B, C and D must
be equal for correct alignment.
Check drive for adequate run-in belt tension. Use the follow-
ing procedure to determine proper belt tension:
Step 1. Measure span length (t) as shown in Figure 28.
Step 2. From Figure 28, the deflection height (h) is always
1/64" per inch of span length (t). For example, a 32"
span length would require a deflection of 32/64" or
1/2".
Step 3. Determine the minimum and maximum recom-
mended pounds force using Table 14. Find the mini-
mum recommended deflection force for the belt
section and type based upon the small sheave diame-
ter. For intermediate sheave diameters and/or drive
ratio combinations, the minimum force may be inter-
polated.
Step 4. Using a spring scale, apply a perpendicular force to
any
one
of the belts at the midpoint of the span as
shown in Figure 28. Compare this value with the val-
ues found in Step 3.
a. If the value is below the minimum, the belts are
too loose and should be tightened.
b.If the value is higher, the belts are too tight and
tension should be decreased.
When new belts are installed, the initial tension will drop.
Check tightness of all setscrews on the fan hub, bearing
sleeves and retighten belts after 48 hours of operation.
Note:
If after all tension adjustments, the belts slip or
squeal when starting, increase tension slightly and
replace the belts if they are worn or glazed.Final
control settings
When all of the start-up procedures have been completed, set
the individual control parameters for operation.
1.
Unit switch S7 to AUTO.
2.
Heating/Cooling control parameters set as required.
3.
Alarm limits set as required.
4.
Night setback parameters set as required.
5.
Duct static pressure, building static pressure, as
required.
6.
Economizer control parameters set as required.
7.
Control timers set as required.
8.
Date and time set as required.
9.
Operating schedule set as required.
10. Holiday schedule set as required.
Note:
See Operation manual per Table 1 on page 3, for the
keypad menu structure.
Maintaining control parameter records
After the unit has been checked, tested and started and the
final control parameters are set, the final settings should be
recorded and kept on file. This file should be updated when-
ever changes are made to the control parameters. This will
facilitate any required analysis and troubleshooting of the
system operation.
Figure 27. Drive Alignment
Figure 28. Belt Tension
Table 14. Recommended Pounds Force Per Belt
BELT
SECTION
SMALL SHEAVE
DIA. (IN)
MINIMUM
MAXIMUM
A
3.0 - 3.6
3.00
4.25
3.8 - 4.8
3.5
5.00
5.0 - 7.0
4.00
5.50
B
3.4 - 4.2
4.00
5.50
4.4 - 5.6
5.13
7.13
5.8 - 8.6
6.38
8.75
BX
3.4 - 5.6
6.50
9.13
4.4 - 5.6
6.50
9.13
5.8 - 8.6
7.38
10.13
5VX
4.7 - 6.7
10.00
15.00
7.1 - 10.8
12.88
18.75
11.8 - 16.0
15.00
22.00
A
B
C
D
FIELD SUPPLIED STRAIGHTEDGE
DEFLECTIO
N
FORCE
SPAN LEN
GTH t
h
D
d
Содержание SWT C Series
Страница 23: ...IM709 23 Typical Wiring Schematics Figure 19 Power Schematic...
Страница 24: ...24 IM709 Figure 20 Input Schematic Discharge Air Control DAC...
Страница 25: ...IM709 25 Figure 21 Input Schematic Zone or Space Comfort Control SCC...
Страница 26: ...26 IM709 Figure 22 Output Schematic Actuator Control...
Страница 27: ...IM709 27 Figure 23 Output Schematic Auxiliary Fan Start Stop Control...
Страница 28: ...28 IM709 Figure 24 Output Schematic Actuator Control...
Страница 29: ...IM709 29 Figure 25 Output Schematic Compressor Control 4 Compressors 4 5 or 6 Stage...
Страница 44: ...13600 Industrial Park Boulevard Minneapolis MN 55441 USA 763 553 5330...