14
IM709
Table 3. Compressor circuit charge
* Charge quantities listed are averages. Actual charge quantity is dependent
on individual unit evaporator coil circuiting. Actual charge quantities are
stamped on each unit nameplate.
Table 4. Compressor application char
t
COMPRESSOR
(HP)
*REFRIGERANT
CHARGE PER
CIRCUIT (R-22)
OIL CHARGE
PER CIRCUIT
(OZ.)
6
9 Ibs.
53
10
14 lbs.
132
13
18 lbs.
128
SWT
MODEL
SIZE
COMPRESSOR HORSEPOWER
MIN.
GPM
(L/s)
MAX
GPM
(L/s)
CKT#1
CKT#2
CKT#3
CKT#4
018C
6
6
-
-
24 (1.5)
42 (2.7)
6
6
6
-
36 (2.3)
62 (4.0)
6
6
6
6
48 (3.0)
84 (5.3)
023C
6
6
6
-
35 (2.2)
65 (4.1)
6
6
6
6
48 (3.0)
84 (5.3)
6
6
6
6
58 (3.7)
102 (6.4)
6
6
6
10
58 (3.7)
102 (6.4)
6
6
10
10
68 (4.3)
119 (7.5)
028C
6
6
6
6
48 (3.0)
84 (5.3)
6
6
6
10
58 (3.7)
102 (6.4)
6
6
10
10
68 (4.3)
119 (7.5)
6
10
10
10
78 (4.9)
137 (8.7)
035C
6
6
6
10
58 (3.7)
102 (6.4)
6
6
10
10
68 (4.3)
119 (7.5)
6
10
10
10
78 (4.9)
137 (8.7)
10
10
10
10
88 (5.6)
154 (9.7)
040C
6
6
6
10
58 (3.7)
102 (6.4)
6
6
10
10
68 (4.3)
119 (7.5)
6
10
10
10
78 (4.9)
137 (8.7)
10
10
10
10
88 (5.6)
154 (9.7)
10
10
13
13
104 (6.5)
183
(11.5)
13
13
13
13
120 (7.6)
212
(13.4)
Содержание SWT C Series
Страница 23: ...IM709 23 Typical Wiring Schematics Figure 19 Power Schematic...
Страница 24: ...24 IM709 Figure 20 Input Schematic Discharge Air Control DAC...
Страница 25: ...IM709 25 Figure 21 Input Schematic Zone or Space Comfort Control SCC...
Страница 26: ...26 IM709 Figure 22 Output Schematic Actuator Control...
Страница 27: ...IM709 27 Figure 23 Output Schematic Auxiliary Fan Start Stop Control...
Страница 28: ...28 IM709 Figure 24 Output Schematic Actuator Control...
Страница 29: ...IM709 29 Figure 25 Output Schematic Compressor Control 4 Compressors 4 5 or 6 Stage...
Страница 44: ...13600 Industrial Park Boulevard Minneapolis MN 55441 USA 763 553 5330...