Service Information
Wiring Diagram
Figure 30. BACdrop Schematic
RJ-45
SBC
L2
L1
GRD
CB
Hot
Neutral
Ground
PS
CN1
CN2
DB9
J1
J13
J22
Network
PC
RJ-45
Ethernet
+
– GRD
DB9
RJ-45
5 Vdc
10BaseT
100 - 240 Vac power supply
Testing Guidelines
If you run into problems with the BACdrop gateway or MicroTech network communications, this
section may give you some ideas on things to look for.
Troubleshooting Power Problems
The BACdrop SBC receives 5 Vdc from the power supply. If the gateway appears to be dead, use the
following guidelines to isolate the problem.
•
If the gateway is not connected to an Ethernet, all of its LEDs will be off. Try cycling power by
opening and then closing circuit breaker CB. The yellow D6 (link) LED should flash when
power is restored. You should also hear at least one beep.
•
Verify that line-voltage power is being supplied to the BACdrop panel and that circuit breaker
CB is closed.
•
Remove the J22 (input power) connector from the SBC and measure the voltage between the
terminals. See Figure 30. The voltage should be 5 Vdc.
If you measure 5 volts, the SBC is probably defective.
If you don’t measure 5 volts, replace the power supply or its cable.