![McQuay IM 689-2 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/mcquay/im-689-2/im-689-2_installation-and-maintenance-data_1756157032.webp)
32
IM 689-2
Figure 12. Typical Cabling Configuration Screen for BACdrop Panel Tools
System Information Tool
The System Information tool displays basic information about the BACdrop gateway and its network
configuration. Some of the information may be useful to you, and some of it may be useful to the
BAS system integration technicians. You can view the information, but you cannot change it with this
tool. See Figure 13.
Figure 13. System Information Tool, BACdrop Screen
Following are brief descriptions of each information field:
BACdrop MAC
(Ethernet) Address
The address of the BACdrop gateway on the Ethernet network. It is
assigned by the manufacturer of the SBC and cannot be changed.
BACdrop MicroTech
Address
The address of the BACdrop gateway on the MicroTech network. This
address can be changed with the BACdrop Setup Wizard’s Configure
Controller List tool. Typically, a BACdrop gateway’s MicroTech address
will be 00.00.
Configured
MicroTech
Controller Count
The total number of MicroTech controllers that have been defined in the
BACdrop configuration file. Usually this number will match the number
of MicroTech controllers on the network, but there can be exceptions; for
example, a series-100 centrifugal chiller’s display processor will exist on
the MicroTech network but will not be configured in the gateway.
Network Numbers
(decimal)
BACnet numbers assigned to the MicroTech network and the BACnet
network that the BACdrop gateway is part of. The BAS system integrator
may supply these numbers. They can be changed with the BACdrop
Setup Wizard’s Configure Network Numbers tool.