Field Wiring
Following are descriptions of the various field wiring requirements. A typical field wiring diagram is
shown in Figure 5. Wiring must comply with the National Electrical Code and all local codes and
ordinances. The warranty is void if wiring is not in accordance with these instructions.
The panel is divided into high and low voltage sections by a sheet metal barrier. The power wiring
should enter the high voltage section through one of the 7/8-inch (22 mm) openings. External
receptacles and a terminal block are provided for the low-voltage communications wiring.
Figure 5. Typical Field Wiring Schematic for MicroTech Network
TS2
BACdrop
Hot
Neutral
100 – 240 Vac
Power
L2
L1
GRD
Notes:
1. Twisted, shielded pair cable must meet the following
minimum requirements: 300 V, 60°C, 20 AWG, polyethylene
insulated, with a PVC outer jacket and drain wire (Belden
8762 or equivalent). Some local codes may require the use
of plenum rated cable.
2. 10BaseT Ethernet cable. To directly connect a PC to the
Ethernet port, a hub or a special crossover cable must be
used.
3. Cable length must not exceed 5000 ft (1524 m).
4. Standard serial cable. A null modem is not required.
See notes 1 & 3
Self-contained AC
Port B
GND
TB7
Reciprocating
chiller
Port B
139
TB4
Screw chiller
Port B
55
BLK
WHT
B+
B–
138
137
54
53
Comm B
UVC (325)
1
2
PNK
GRY
Comm B
UVC (125)
4
5
PNK
GRY
RJ-45
3rd-party BAS
See note 2
TB1
Centrifugal chiller
(series 200)
Port B
85
86
84
TB2
Applied rooftop
Port B
130
128
129
Legend
Field wiring terminal
Field wiring: discrete
Factory wiring
Field wiring: twisted, shielded pair cable
with drain wire
(see note 1)
B+
Crimp or solder splice
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
Comm B
UVC (325)
1
2
PNK
GRY
Comm B
UVC (325)
1
2
PNK
GRY
Comm B
UVC (325)
1
2
PNK
GRY
Ethernet
DB9
PC
PC
+
–
GRD
Network
See note 4
Field wiring: 10BaseT Ethernet
Standard serial cable