background image

 IM 422-4 / Page 13 (Rev. 5/99)

TROUBLE

CAUSE

CURE

8. Insufficient cooling

capacity (continued).

9. Too much cooling.

10. “Sweating”

11. Blowers won’t operate

on HEAT.

12. **Equipment is noisy.

13. Insufficient or no heat.

f.

Compressor not pumping, indicated by:
1) Low wattage.
2) Condenser not warm, evaporator only partially cool or

not at all.

g. Restricted capillary tube or strainer, indicated by:

1) Frost on capillary or strainer.
2) Low wattage.
3) Condenser not warm.
4) Evaporator partially frosted, only partially cool or not at

all.

a. Thermostat set too low.
b. Defective thermostat.

a. Condensate drain from evaporator to condenser plugged.
b. Insulating seals on equipment damaged.
c. Evaporator blower motor not up to speed.
d. Evaporator blower incorrectly positioned.

a. No power.
b. Heat is off (equipment with heat fan lockout).
c. Faulty pushbutton switch.
d. Loose connections at pushbutton switch.
e. Thermostat set too low.

a. Blower rubbing against enclosure.

b. Blower motor bearings are dry.
c. Loose blower hold-down nuts on motor-bracket assembly.
d. Refrigerant absorbed in compressor oil after extended

shutdown.

e. Equipment improperly installed.
f.

Damper solenoid hums.

g. Loose terminal box cover on side of compressor.
h. Loose electrical components.
i.

Copper tubing vibrating.

j.

Harmonics.

k. Loose sheet metal parts.

a. No steam or hot water being applied.
b. No power.

c. Faulty pushbutton switch.
d. Loose connection at pushbutton switch.
e. Thermostat set too high.
f.

Thermostat faulty.

g. No power output on transformer secondary.
h. Inoperative valve.

1) Steam valve N/C.
2) Hot water valve N/O.

f.

*Ship prepaid to nearest McQuay authorized warranty station.

g. 4) *Ship prepaid to nearest McQuay warranty station.

a. Adjust.
b. Replace.

a. See No. 1.
b. Open heat valve or turn on heating system.
c. Check for correct voltage. Oil motor if necessary.
d. Adjust.

a. See No. 1.
b. Open heat valve or turn on heating system.
c. Replace.
d. Tighten.
e. Adjust. Rotate control knob to “Warmer.”

a. Adjust fan position on motor shaft or reposition fan motor

bracket assembly.

b. Lubricate with SAE No. 10 or replace motor.
c. Align blower assembly and tighten nuts.
d. Noise will disappear after equipment runs awhile.

e. Make necessary adjustments to components.
f.

Check for proper adjustment. Apply silicone oil or grease to
gap between solenoid and armature.

g. Tighten.
h. Fasten securely.
i.

Adjust by bending or applying tape.

j.

Occasionally equipment will have noisy operation for no ap-
parent reason. Inspection has revealed no loose components
that might be the source of the noise. Due to the action of the
compressor, it is possible to have internal noise develop if the
refrigerant tubing has become bent even slightly. To distin-
guish this condition from the simple rattle producing vibration
caused by loose screws, nuts and other components, grasp
the refrigerant tubing at various points throughout the system
until a point is found where the noise is eliminated or reduced.
Bend the copper tubing very gently until the noise disap-
pears.

k. Tighten.

a. Contact building management.
b. Check power supply line fuses, circuit breakers. Blown fuses

would indicate circuit overloading, a short circuit, or a grounded
condition in the circuit.

c. Replace.
d. Replace wire or tighten.
e. Adjust rotate knob to “Warm.”
f.

Replace.

g. Replace.
h.

1) Temporary lock valve open; replace.
2) Replace.

Troubleshooting Chart

These items should be checked by a qualified service techician only.

Notes: This guide was prepared with standard equipment in mind. If equipment is special, it may not be entirely applicable.

* If equipment is still in warranty.

** Note: Before trying to correct the noise,  determine its cause: conditioned air blower, compressor or condenser blower. Operate the conditioned air blowers only.
If this doesn’t cause the noise, operate on cooling. Then disconnect one compressor lead. If the noise stops, the compressor is the source. If not, it is caused by
the condenser blower.

Chassis:
Size 007 . . . . . . . . . . . . . . . . . . . . . . . . . . .  141 lbs. (64 kg)
Size 009 . . . . . . . . . . . . . . . . . . . . . . . . . . .  145 lbs. (66 kg)
Size 012 . . . . . . . . . . . . . . . . . . . . . . . . . . .  149 lbs. (68 kg)
Size 015 . . . . . . . . . . . . . . . . . . . . . . . . . . .  153 lbs. (69 kg)

Wall Sleeve:

 

Uninsulated . . . . . . . . . . . . . .  36 lbs. (16 kg)

Hydronic Heat Section:
Steam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12 lbs. (5 kg)

Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12 lbs. (5 kg)

Room Cabinets:
Standard 10

3

4

" (273mm) depth . . . . . . . . . .  60 lbs. (27 kg)

For each additional inch of room cabinet depth add 4 lbs. (2 kg)
to the standard depth cabinet.

Louvers:

 

Architectural . . . . . . . . . . . . . . . . . . .  8 lbs. (4 kg)

Approximate Shipping Weights

Содержание 106018561

Страница 1: ...McQuay Incorporated Incremental Comfort Conditioners Suite II With Top Mounted Hydronic Heat Section Installation Maintenance Data Group PTAC Part No 106018561 Date May 1999 IM 422 4 Page 1 Rev 5 99...

Страница 2: ...installer exercise caution This equipment is to be installed only by an experienced installation company which employs trained personnel Inspection When the equipment is received all items should be c...

Страница 3: ...Piping Rough in Typ R H L H 3 76mm Min 3 76mm Kickplate Removable Front 7 8 22mm Wall Thickness C A 11 4 32mm 27 8 67mm 16 406mm B 91 8 232mm 51 2 140mm 7 8 22mm 15 8 41mm 15 16 33mm 3 76mm Min Kickp...

Страница 4: ...uctions For panel wall and thin wall construction it is recommended that the optional top angle be used and the wall sleeve be supplied with a turned down flange see Figure 3 The recommended procedure...

Страница 5: ...nd the finished wall surface This is to accommodate the heat section and room cabinet The center of gravity is 103 4 273mm from the rear face of the standard wall sleeve If no subbase is being employe...

Страница 6: ...the brickstop contacts the exterior bricks as illustrated below If a brickstop is not used slide the wall sleeve in the wall so that it extends into the room a minimum of 11 8 29mm beyond the finishe...

Страница 7: ...supplied and pipe it according to the illustration Install valve and other accessories including air vents steam traps stop balance valves etc as specified by the design engIneer 5 For valve installed...

Страница 8: ...the condenser coil cover 8 If louver has not been previously installed connect to wall sleeve as described above 9 If louver is supplied by others as illustrated in Figure 4 page 5 be sure to install...

Страница 9: ...the hold down screw 4 Screw the cabinet to the wall using the screws provided There are two 2 screw holes provided on each side located on the inner flanges of the room cabinet 5 Loosen the four 4 win...

Страница 10: ...ld provide uninterrupted service for many years Scheduled maintenance of this equipment as described below is the key to the equipment s longevity 1 Air filters must be cleaned at regular intervals Tw...

Страница 11: ...0 Units Cooling Chassis 1 Compressor Overload Device 1 Compressor Running Capacitor 1 Evaporator Fan Motor 1 Condenser Fan Motor 1 Pushbutton Switch 2 Damper Switch 2 Thermostat 2 Knob for Thermostat...

Страница 12: ...nly TROUBLE CAUSE CURE 1 Blowers won t operate on COOL 2 Blowers operate on COOL but compressor doesn t start 3 Blowers run on COOL and compressor starts but stops after a short interval 4 Blowers run...

Страница 13: ...or c Align blower assembly and tighten nuts d Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to...

Страница 14: ...IM 422 4 Page 14 Rev 5 99 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Open Valve...

Страница 15: ...IM 422 4 Page 15 Rev 5 99 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Closed Valve...

Страница 16: ...of the product is other than that published by the Company One Year Refrigeration Circuit Warranty Hermetically sealed motor compressor assemblies and all components of refrigeration circuits not read...

Отзывы: