background image

 IM 422-4 / Page 5 (Rev. 5/99)

Applications utilizing field supplied louvers require additional
considerations:

1. Louvers supplied by others must have 70% free area or a

pressure drop not exceeding 0.05 in. w.g. (12.45 Pa) at
300 fpm (1.524 m/sec) face velocity, and a blade design
that will not cause recirculation of air.

2. McQuay does not warrant the rain and water leakage

resistance of its equipment when used with louvers by
others.

3. All louvers by others must be approved by the manufac-

turer prior to installation.

Figure 4 illustrates a typical installation using a field

supplied, continuous louver. This method is for illustration
purposes only. Other variations may be employed as long as
they meet manufacturer’s louver specifications listed above
and so long as adequate wall support is achieved. All struc-
tural supports and fasteners (except the optional top angle
and turned down flange) are field supplied.

Installation of wall sleeves with continuous louvers is very

similar to that of applications with factory furnished louvers.
Assuming the louver meets the manufacturer’s criteria, as
stated previously, proceed to install the wall sleeve as follows:

Wall Sleeve Installation — Thin Wall Construction

1. Clean the opening of all debris that may interfere

with 

installation.

2. Position the wall sleeve into the wall so that it is flush with

the exterior wall. Important: If the wall sleeve has been
installed into a thick wall, make certain the wall sleeve
protrudes into the room a minimum of 1

1

8

" (29mm) beyond

the finished wall surface. This is to accommodate the heat
section and room cabinet. The center of gravity is 10

3

4

"

(273mm) from the rear face of the standard wall sleeve. If
no subbase is being employed, adequate support for the
wall sleeve up to the center of gravity must be provided at
the job site. This support can be wood, metal or concrete.

3. Level wall sleeve in all directions and anchor with appro-

priate fasteners using holes provided (see Figure 14, page
8), or drill additional holes as required to secure firmly.
Caution: Do not drill holes in the base of the wall sleeve.
Use shims between the wall and the wall sleeve to prevent
wall sleeve distortion during anchoring.

4. Caulk the wall sleeve to the wall opening on both the inside

and outside perimeter. This can be done from the inside of
the building. Be careful not to plug the weep holes.

Figure 4. Wall sleeve installation using top angles and field supplied continuous louver

13

3

4

"

(349mm)

1

1

4

"

(38mm)

Insulated

Panel

Optional

Top Angle

16"

(406mm)

Outside Edge
of Sleeve

Wall Sleeve

Turndown

Flange

(See Detail)

Finished Floor

Including Carpet

Outside Louver
By Others

Resilient
Caulking

Turndown
Flange

Resilient
Caulking

Wall

Sleeve

Wall

Frame

By Others

Optional

Top Angle

42"

(1069mm)

Optional

Subbase

16"

(406mm)

10

1

2

"

(267mm)

Max.

1"

(25mm)

3"

(76mm)

Min.

Wall

Sleeve

Insulated

Panel

Notes:
1. Caulk entire perimeter of wall sleeve after installation.
2. Seal area between louver and wall sleeve to prevent con-

denser air recirculation.

3. Dimensions shown in table on page 3 do not apply to this

application.

*Dimension “Y” is field determined or specified. Angle is factory
welded at given dimension when option is designated.

Y*

Supports By Others

(2 Req’d.)

Min. 3

7

8

"

(98mm)

Содержание 106018561

Страница 1: ...McQuay Incorporated Incremental Comfort Conditioners Suite II With Top Mounted Hydronic Heat Section Installation Maintenance Data Group PTAC Part No 106018561 Date May 1999 IM 422 4 Page 1 Rev 5 99...

Страница 2: ...installer exercise caution This equipment is to be installed only by an experienced installation company which employs trained personnel Inspection When the equipment is received all items should be c...

Страница 3: ...Piping Rough in Typ R H L H 3 76mm Min 3 76mm Kickplate Removable Front 7 8 22mm Wall Thickness C A 11 4 32mm 27 8 67mm 16 406mm B 91 8 232mm 51 2 140mm 7 8 22mm 15 8 41mm 15 16 33mm 3 76mm Min Kickp...

Страница 4: ...uctions For panel wall and thin wall construction it is recommended that the optional top angle be used and the wall sleeve be supplied with a turned down flange see Figure 3 The recommended procedure...

Страница 5: ...nd the finished wall surface This is to accommodate the heat section and room cabinet The center of gravity is 103 4 273mm from the rear face of the standard wall sleeve If no subbase is being employe...

Страница 6: ...the brickstop contacts the exterior bricks as illustrated below If a brickstop is not used slide the wall sleeve in the wall so that it extends into the room a minimum of 11 8 29mm beyond the finishe...

Страница 7: ...supplied and pipe it according to the illustration Install valve and other accessories including air vents steam traps stop balance valves etc as specified by the design engIneer 5 For valve installed...

Страница 8: ...the condenser coil cover 8 If louver has not been previously installed connect to wall sleeve as described above 9 If louver is supplied by others as illustrated in Figure 4 page 5 be sure to install...

Страница 9: ...the hold down screw 4 Screw the cabinet to the wall using the screws provided There are two 2 screw holes provided on each side located on the inner flanges of the room cabinet 5 Loosen the four 4 win...

Страница 10: ...ld provide uninterrupted service for many years Scheduled maintenance of this equipment as described below is the key to the equipment s longevity 1 Air filters must be cleaned at regular intervals Tw...

Страница 11: ...0 Units Cooling Chassis 1 Compressor Overload Device 1 Compressor Running Capacitor 1 Evaporator Fan Motor 1 Condenser Fan Motor 1 Pushbutton Switch 2 Damper Switch 2 Thermostat 2 Knob for Thermostat...

Страница 12: ...nly TROUBLE CAUSE CURE 1 Blowers won t operate on COOL 2 Blowers operate on COOL but compressor doesn t start 3 Blowers run on COOL and compressor starts but stops after a short interval 4 Blowers run...

Страница 13: ...or c Align blower assembly and tighten nuts d Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to...

Страница 14: ...IM 422 4 Page 14 Rev 5 99 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Open Valve...

Страница 15: ...IM 422 4 Page 15 Rev 5 99 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Closed Valve...

Страница 16: ...of the product is other than that published by the Company One Year Refrigeration Circuit Warranty Hermetically sealed motor compressor assemblies and all components of refrigeration circuits not read...

Отзывы: