background image

IM 422-4 / Page 8 (Rev 5/99)

Anchoring

Anchoring the wall sleeve in the opening is accomplished as
shown in Figure 14. It is recommended that rubber isolation
washers be used with the fasteners to minimize sound
transmission from the equipment to the wall, at the point of
contact.

5

16

" (8mm) hole is provided on each side, 2" (51mm)

down from  the top and 2" (51mm) in from the rear of the wall
sleeve. It may be necessary to drill additional holes in the wall
sleeve to firmly secure it. Caution: Do not drill holes in the
base of the wall sleeve. Use shims between the wall and the
wall sleeve to prevent sleeve distortion during anchoring.

Installation of Cooling Chassis

Correct installation of the cooling chassis is extremely impor-
tant to insure the proper operation of the unit. Install the
chassis as follows:

1. Remove outer carton and inspect for any shipping dam-

age. Report any found to the carrier.

2. Check nameplate data on chassis to insure that the

correct job site distribution has been made with respect
to cooling capacities. Generally, corner rooms require
larger capacities.

3. Remove chassis from carton by pulling evenly on sub-

stantial portion of unit. Caution: Do not pull on evaporator
fan housing, control box or compressor.

4. If wall sleeve has been previously installed, remove

temporary weather panel.

5. Check all fasteners to make certain they have not come

loose during shipment. Do not loosen nuts holding down
compressor; they are set at the factory.

6. Do not lubricate motors before start-up. Motors are

factory lubricated. Consult “Scheduled Maintenance”
section on page 12 for lubrication instructions.

7. Place Tinnerman clips from bag onto wall sleeve. Clips

and mounting screws are enclosed in a bag attached to
the top of the condenser coil cover.

8. If louver has not been previously installed, connect to

wall sleeve as described above.

9. If louver is supplied by others, as illustrated in Figure 4,

page 5, be sure to install foam type gaskets on all sides
of the condenser coil to prevent recirculation or bypass of
condenser air.

10. Slide chassis into wall sleeve until firmly seated against

weather seals of wall sleeve. Caution: Do not push on

Installation of Louvers

1. Remove louver from its shipping carton which also con-

tains a hardware package for mounting the louver.

2. Remove outside weather plug and weather panel from wall

sleeve.

3. Make a temporary handle by looping a piece of flexible

wire or heavy cord through the louver. This enables the
installer to keep a firm grasp on the louver when installing
from inside the room.

4. Push the louver through the opening at the rear of the wall

box, then pull the louver back to the wall sleeve flange so
that the louver studs pass through the holes in the flange.

5. Attach washers and nuts and secure louver in place.

6. If the cooling chassis is not to be immediately installed,

replace the weather panel.

coil surface or control box cover. Make sure the com-

pres

sor tubing does not catch when inserting chassis.

11. Secure chassis  to wall sleeve with four (4) sheet metal

screws packaged with the Tinnerman  clips.

12. Plug electrical cord into receptacle. Excess cord should

be coiled up neatly and stored in the conditioner.

13. Set the manual damper operator in open or closed

position as desired. On units equipped with the optional
electric fresh air damper, set the “Auto-Off” switch in the
desired position. In “Auto,” the damper is open whenever
the indoor fan motor is running. The “Auto-Off” switch is
located on the bottom front face of the control box.

Expansion

Anchor

Bolt

Molly or

Toggle Bolt

Cripple Stud

Main Stud

Wood

Screw

Factory
Supplied
Holes (2)

Chassis

Damper
Actuator

Hydronic
Heat
Sect.

Wall Sleeve

Содержание 106018561

Страница 1: ...McQuay Incorporated Incremental Comfort Conditioners Suite II With Top Mounted Hydronic Heat Section Installation Maintenance Data Group PTAC Part No 106018561 Date May 1999 IM 422 4 Page 1 Rev 5 99...

Страница 2: ...installer exercise caution This equipment is to be installed only by an experienced installation company which employs trained personnel Inspection When the equipment is received all items should be c...

Страница 3: ...Piping Rough in Typ R H L H 3 76mm Min 3 76mm Kickplate Removable Front 7 8 22mm Wall Thickness C A 11 4 32mm 27 8 67mm 16 406mm B 91 8 232mm 51 2 140mm 7 8 22mm 15 8 41mm 15 16 33mm 3 76mm Min Kickp...

Страница 4: ...uctions For panel wall and thin wall construction it is recommended that the optional top angle be used and the wall sleeve be supplied with a turned down flange see Figure 3 The recommended procedure...

Страница 5: ...nd the finished wall surface This is to accommodate the heat section and room cabinet The center of gravity is 103 4 273mm from the rear face of the standard wall sleeve If no subbase is being employe...

Страница 6: ...the brickstop contacts the exterior bricks as illustrated below If a brickstop is not used slide the wall sleeve in the wall so that it extends into the room a minimum of 11 8 29mm beyond the finishe...

Страница 7: ...supplied and pipe it according to the illustration Install valve and other accessories including air vents steam traps stop balance valves etc as specified by the design engIneer 5 For valve installed...

Страница 8: ...the condenser coil cover 8 If louver has not been previously installed connect to wall sleeve as described above 9 If louver is supplied by others as illustrated in Figure 4 page 5 be sure to install...

Страница 9: ...the hold down screw 4 Screw the cabinet to the wall using the screws provided There are two 2 screw holes provided on each side located on the inner flanges of the room cabinet 5 Loosen the four 4 win...

Страница 10: ...ld provide uninterrupted service for many years Scheduled maintenance of this equipment as described below is the key to the equipment s longevity 1 Air filters must be cleaned at regular intervals Tw...

Страница 11: ...0 Units Cooling Chassis 1 Compressor Overload Device 1 Compressor Running Capacitor 1 Evaporator Fan Motor 1 Condenser Fan Motor 1 Pushbutton Switch 2 Damper Switch 2 Thermostat 2 Knob for Thermostat...

Страница 12: ...nly TROUBLE CAUSE CURE 1 Blowers won t operate on COOL 2 Blowers operate on COOL but compressor doesn t start 3 Blowers run on COOL and compressor starts but stops after a short interval 4 Blowers run...

Страница 13: ...or c Align blower assembly and tighten nuts d Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to...

Страница 14: ...IM 422 4 Page 14 Rev 5 99 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Open Valve...

Страница 15: ...IM 422 4 Page 15 Rev 5 99 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Closed Valve...

Страница 16: ...of the product is other than that published by the Company One Year Refrigeration Circuit Warranty Hermetically sealed motor compressor assemblies and all components of refrigeration circuits not read...

Отзывы: