2012 Mobile Climate Control
T-348 Rev. 07/2012
Table 3-2. Alarm Codes - Continued
ALARM
NO
TITLE
CAUSE
REMEDY
CONTROLLER
RESPONSE
A22
Breaker Trip/Blown Fuse
Alarm
A breaker/fuse on the
relay board has tripped
or a fan relay has failed.
Check breakers/fuse for
tripped device. Repair
short and reset/replace
breaker/fuse.
Alarm will be generated.
A23
Evaporator Fan Overload
Evaporator fan overload
jumper is open.
Ensure connector is
plugged in or repair
wiring.
Alarm will be generated.
A24
Condenser Fan Overload
Condenser fan overload
jumper is open.
Ensure connector is
plugged in or repair
wiring.
Alarm will be generated.
A25
Not used
A26
Not used
A31
Maintenance Alarm 1
The compressor hour
meter is greater than the
value in Maintenance
Hour Meter 1.
Reset the maintenance
hour meter.
Alarm will be generated.
A32
Maintenance Alarm 2
The evaporator hour me
ter is greater than the
value in Maintenance
Hour Meter 2.
Reset the maintenance
hour meter.
Alarm will be generated.
A33
Low Pressure Warning
Suction pressure low
enough to energize UV2.
Check cause of low suc
tion pressure. (Refer to
section 3.3.4)
Alarm will be generated.
A34
High Pressure Warning
Discharge pressure high
enough to
energize UV2.
Check cause of high dis
charge pressure. (Refer
to section 3.3.4)
Alarm will be generated.
A99
Alarm Queue Full
All locations of the alarm
queue are currently full
and no more alarms can
be saved.
Record and clear alarm
queue.
Alarm will be generated.