MBS UGW
maxi
| Mk II
User interface, operation and functions
43 of 54
Connect timeout
Timeout for establishing a modem connection. If no connection is
established within this time, it counts as a connection attempt. There is
a maximum number of
APDU retries
(connection attempts).
IDLE timeout
If no relevant data are transferred within this time during a connection,
the connection is terminated.
Automatic dial-up
Determines which BACnet services are the subject of a connection
attempt. This is a list of “confirmed” and “unconfirmed” items with the
BACnet enumeration of services.
•
C2 – Confirmed Event Notification
•
U3 – Unconfirmed Event Notification
•
C15 – Confirmed Write Property (initiated by MBS Gateway)
•
C16 – Confirmed Write Property Multiple
(initiated by MBS Gateway)
Incoming password
BACnet PTP password for dialling-up the universal gateway.
External networks
The external networks that can be accessed via BACnet PTP are
configured here. The network number indicates the accessible
BACnet network. You can specify up to three telephone numbers
under which the BACnet counterpart station can be reached. These
are dialled consecutively by a modem as part of the “Connect timeout”
phase. The password is used to log into the counterpart station.
BACnet > Device object
The BACnet device object in the universal gateway has a specific
function that the other BACnet objects don’t have. APDU parameters
for BACnet transmission are set here. The device instance and device
name can also be set.