User interface, operation and functions
45 of 54
Model name
UGW model designation.
Firmware revision
Firmware version of the UGW software.
APDU max. length accepted
Maximum telegram size in bytes.
The following values are possible: 50, 206, 480, 1024 and 1476 bytes.
APDU timeout
This value in milliseconds defines the period of time after which an
acknowledgement-dependent telegram is deemed to have failed in
the absence of confirmation. The default value is 3000 ms.
APDU retries
This value defines how often a failed telegram is to be repeated
(Standard = 5).
APDU segmentation supported
Possible values: 0-both, 1-transmit, 2-receive, 3-no
APDU max. segments accepted
Defines how many segments are accepted as a maximum.
APDU segment timeout
This value defines the period of time after which an
acknowledgement-dependent, segmented telegram is deemed to
have failed in the absence of segment confirmation
(Standard = 2000 ms).
BACnet > Objects
The BACnet object configuration is displayed here. Data points can be
filtered according to object type using the upper panel of buttons. The
available BACnet objects are listed below.
Object names and descriptions can be edited directly in the input
fields in the object list.