BACnet > Settings
General settings for the BACnet driver and the BACnet data links are
made here. Clicking
<Save>
, closing the dialogue box and carrying out
a simple restart of the gateway will apply the changes.
Start delay
Here, you can set a start delay for BACnet failure detection. When
restarting the UGW, BACnet communication will only be switched on
after this time has elapsed. This allows a remote station to recognise if
the UGW has been restarted by the absence of BACnet requests. The
value “0” sends a
BACnet restart notification
message as an
unconfirmed COV notification to the registered recipient when
restarting.
DCC/RD password
You can set a password (max. 50 characters) to protect DCC (Device
Communication Control) and RD (Reinitialize Device) BACnet services.
The password is case-sensitive.
Default priority
Set the default priority.
Disable Default-NC-Object
Disables requirement for a Notification Class Object (NC).