MBS UGW
maxi
| Mk II
User interface, operation and functions
38 of 54
Data links
You can set which BACnet data links are to be used via the
Data links
drop-down list.
The following are supported:
•
BACnet IP (Ethernet)
•
BACnet MS/TP (two-wire connection) via RS485
•
Simultaneous BACnet IP and BACnet MS/TP.
BACnet PTP
By checking this box, you can enable communication via the
Point-To-
Point
BACnet half-router in addition to the BACnet data links. This is
necessary for BACnet operation with a modem.
A) Gateway mode: Data links = BACnet IP
The following operating types are possible for BACnet IP connection:
Normal, BACnet BBMD (BACnet Broadcast Management Device) and
BACnet Foreign Device.
BACnet BBMD and FD configuration is necessary for operation of the
entire IP network. To ensure this is set up correctly, you may have to
contact the BACnet network coordinator.
a) IP mode = normal