User interface, operation and functions
41 of 54
B) Gateway mode: Data links = BACnet MS/TP
BACnet MS/TP is the connection for BACnet devices via the RS485
(two-wire) interface. The necessary settings can be made here. To
ensure this is set up correctly, you may have to contact the BACnet
network coordinator.
Network number
Defines the network number of the BACnet network for the data link.
The value is between 1 and 65,534.
MS/TP address
Defines the MS/TP MAC address.
Max. master
The property
Max. master
defines the highest MAC address for master
nodes in the MS/TP subnetwork. The possible value range is between
0 and 127; the default value is 127. If this value is not writeable via
BACnet services, it must be 127.