MBS UGW
maxi
| Mk II
User interface, operation and functions
39 of 54
Network number
Defines the network number of the BACnet network for the data link.
(Value = 1 … 65,534).
Notice
The network numbers of the configured data links must be unique
within the network.
LAN name
Name of the data link interface
UDP port
Defines the UDP port of the BACnet/IP network as a decimal number.
The default value is 47808 (“0xBAC0” – hexadecimal).
IP mode
Defines the gateway’s IP mode for this data link.
•
Normal
: Standard operating mode for a BACnet IP data link
•
BBMD
: Operating mode as “BACnet Broadcast Management
Device”.
•
Foreign Device
: Operating mode as “Foreign Device”
b) IP mode = BBMD
The gateway provides BBMD functionality for its own IP subnetwork
and allows logins of external FD or BBMD devices.