MBS UGW
maxi
| Mk II
User interface, operation and functions
42 of 54
Max. info frames
Defines the maximum number of telegrams that a master node may
send before the token has to be forwarded. The possible value range
is between 1 and 127; the default value is 1. If this property is not
writeable via BACnet, this value must be 1.
Serial interface
Defines the serial interface of the data link.
Baud rate
Speed of the MS/TP network apposite to the other MS/TP components
that are used. The value is stated in bit(s); possible values are: 9600,
19200, 38400, 57600, 76800 and 115200 baud. The default value is
76800 baud.
C) Gateway mode: BACnet PTP = activated
BACnet Point-To-Point is designed for communication via null-modem.
The UGW is a half-router in BACnet PTP mode. Together with the dial-
up part, it constitutes a BACnet router for a complete BACnet network.
The BACnet networks must be configured correspondingly. The
network number helps identify a BACnet network and must be unique
within the entire BACnet network.
This mode is currently unavailable.
Содержание maxi Mk II
Страница 1: ...MANUAL maxi Mk II Dated 2020 01...
Страница 54: ...MBS UGW maxi Mk II Conformity 54 of 54 10 Conformity...