To operate, push each of the toggle switches ON-OFF, START-STOP and TEST-RESET to the desired function.
* Switch the power ON to unit. Select required batch quantity using rotary number dial selector switches.
* RESET unit. The LED displays zero and all LED indicators and alarm turns off. The unit is ready for batching.
* START unit; voltage contact drive activates. CONTACT DRIVE LED illuminates indicating pump or solenoid are energized,
followed by FLOW LED illuminating, indicating pulsing and operation of flowmeter. The digits begin counting upward towards the
selected batch quantity.
* Upon digits reaching the selected batch quantity the alarm sounds (short beep) indicating completion of batch; CONTACT DRIVE
and FLOW LEDs turn off. LED display digits and selected batch quantity should correspond. If LED digits overshoot target, use
PREACT (inflight,freefall) overflow deduct dials (located at rear of controller unit) to scale back the difference.
* To interrupt unit before completion of batch, push STOP toggle; digit counting will stop, drive contact off. Push START toggle to
resume batch.
* TEST toggle is used to test digit counting, switch contacts, alarm conditions or generate output pulses for computer interfacing.
TEST does not activate pump or solenoid.
Warning: if CONTACT or FLOW LED indicators are on, but controller is not counting, discontinue use and call for service.
CALIBRATION
1) The Batch Controller is initially set up for the connected flowmeter using
the Controller’s Calibration rotary selector knobs (at rear of unit) marked
UNITS, TENS and HUNDREDS to match flowmeter’s output pulse value.
Note reverse sequence of dials: e.g. U=0, T=0, H=3, is a value of 300.
On-site calibration adjustment and test:
2) Must adjust what is shown on the Batch Controller display (red LEDs) to
match a known amount dispensed, using the Calibration knobs. So, set
Controller to 190L, and batch into a 200 litre (44 gallon) drum.
3) If the amount collected is
more
than is shown on the LED display, then
decrease
the set calibration value by the same % difference
e.g. if collected 200L when 190L on LEDs, this is 10L more or 5% over
(10/190x100%). So, decrease the calibration value by 5% i.e. if calibration set to
300, new value is 300-5% = 300-15 = 285 (Set Calibration U=5, T=8, H=2).
4) If the amount collected is
less
than is shown on the LED display, then
increase
the set calibration value by the same % difference.
e.g. if collected 180L when 190L on LEDs, this is 10L less or 5% under
(10/190x100%). So, increase the calibration value by 5% i.e. if calibration set to
300, new value is 300+5% = 300+15 = 315 (Set Calibration U=5, T=1, H=3).
Example pulse flowmeter calibration settings
Note: x17 pulse input multiplier is used to enhance
calibration resolution if flowmeter has <58 pulses/Litre.
Flowmeter
Size Ø
H T U
Signal input
multiplier
RPFS
25mm
0 7 5
x1
PMS25
25mm
1 0 0
x 1
RPFS
32mm
7 8 2
x17
RPFS
40mm
5 1 0
x17
RPFS
50mm
3 4 0
x17
RPFS
80mm
1 2 4
x17
RPFS
100mm
0 7 8
x17
5)
PREACT:
Calibrating inflight overflow is via two rotary select knobs marked "TENS" and
“UNITS” of LITRES, located at the rear of controller. Simply set knobs to same overflow reading as
indicated by the LED display.
Example: You select 190 Litres, batch the quantity, 200 Litres is shown on display, and 200 Litres
is collected in drum. A valve may take extra time to close, so what is selected on dials usually
overshoots on display. So, set 10 Litres on PREACT to deduct the 10 Litres overshoot (PREACT
T=1, U=0 is a value of 10 Litres). Next batch, the selector Dials, LED reading and amount collected
in drum are all 190 Litres.
SPECIFICATIONS
ME995-7
Power supply
220-
260vac (optional 24,110 vac or 12-24 VDC)
Output to flowmeter
12 VDC upto 100mA
Relay outputs
Standard Max. 240 vac, 1 A.
(Other outputs as per spec. option ordered)
Frequency input
5 KHz: x1 input, 340 Hz: x17 input.
(min.10hz)
Display
4 digits, 7 segment LED (14mm H)
Connection
10 pin Weidmuller mating plug & socket
Fuse
1 Amp (5 x 20mm case)
Batch selection
Visual rotary select knob switches
Batch commands
Push toggle switches
Mounting
Panel mount
Weather Rating
Indoor only IP51
(for outdoor use HB2510 box)
Instrument housing
ABS hi-impact case mould
External dimensions
206 L, 130 H, 90 D mm
Panel cutout
190 L, 122 H mm
Weight
1 kg
Due to continuous product improvement, specifications are subject to change without notice.
ORDERING CODES
ME995-7
ME995-7
Batch Controller, 240 vac supply and output, with 12 VDC power to flowmeter (standard).