background image

 

Page 1

 

TROUBLE SHOOTING GUIDE 

 

Manu

Flo

 

®

TM

 

FOR BATCH CONTROLLER / ROTA PULSE FLOW METER SYSTEMS 

 
PROBLEM 

 

 

POSSIBLE CAUSE 

 

SUGGESTED SOLUTION 

No power to batch controller   

Blown fuse or holder not tightened 

Check fuse, tighten fuse holder (at rear of controller) 

 or displays not on   

 

+12vdc and O.V. shorted 

 

Check pulse cable from DCD to RPFS meter 

 

 

 

 

No main power supply 

 

Check power supply, check wiring 

Pulse fails at start of batch   

•Check calibration (K-factor) setting 

•000 calibration -pulsefails. Make sure a calibration value is set,  

(1.5 seconds after)   

 

 

 

 

 

  three switch shafts -H,T,U- located at rear top left of controller 

 

 

 

 

Seized paddlewheel 

 

Remove RPFS, inspect; if calcium buildup clean with diluted acid,     

                                                                                                                                check axle/bushes, make sure paddlewheel spins freely. 
 

 

 

 

Solenoid valve not opening   

Check and service solenoid valve, check output control voltage is 

 

 

 

 

 

 

 

 

  240vac(N & C, pins 7&9) when pushing start button. Or other    

                                                                                                                                voltage as per specification output 
 

 

 

 

Restriction or service gate valve closed 

Open gate valve 

 

 

 

 

Empty water tank,   

 

Check water level 

 

 

 

 

Pump not turning   

 

Check and service pump 

 

 

 

 

•Pump foot valve failed 

 

•Empty pipe, Install non-return valve 

 

 

 

 

 

 

Signal cable cut, bad joint at JB, 

Check signal cable for 12VDC at junction box near RPFS meter 

 

 

 

 

  oxidized cable- leakage 

 

  If no power, cable cut or oxidized- repair/replace.  

 

 

 

 

 

 

 

 

  Unwire RPFS, take up to batchroom, remove extension cable & 

 

 

 

 

 

 

 

 

  hardwire RPFS direct into the Batch controller (P,+,-), spin wheel 

 

 

 

 

 

 

 

 

  should count on display, if so, then extension cable or connections  

 

 

 

 

 

 

 

 

  at JB faulty, if no counts & 12vdc present then RPFS faulty 

 

 

 

 

•RPFS not positioned in pipe   

•Check RPFS slots are in keyway position, lock cap secured 

 

 

 

 

 

 

 

 

  Paddlewheel not inserted into flow stream 

 

 

 

 

RPFS Flowmeter faulty 

 

Replace with new RPFS  

Pulse fails during batch cycle  

Flowrate too slow   

 

Open restriction gate valve, or increase flowrate pulse fail  

 

 

 

 

 

 

 

 

  timing capacitor (see service guide). Pipe diameter too big for flow 

 

 

 

 

Pipe buildup restricting flow   

Cleanout pipelines, calcium buildup on pipe walls -recycle systems 

 

 

 

 

Paddlewheel problem 

 

Calcium buildup on wheel, soak in diluted acid. Warn bushes. 

 

Display digits count slowly 

 

Non return valve faulty  (jammed open) 

Clean, service or replace 

  after batch complete 

 

•Solenoid valve not properly closed 

•damaged seal, faulty solenoid 

 

Batch target display counter   

Flowrate too fast excessive overflow 

Turn down gate valve to restrict flowrate 

  counts past batch selection    

 

 

 

 

  or set pre-act (overflow deduct) function to compensate 

 

 

 

 

 

 

 

 

Reduce delivery pipe diameter 

•Intermittent overflow past batch select  •Faulty solenoid valve not closing 

•service solenoid valve, check air pressure 

 or water does not stop   

 

 properly, insufficient air pressure 

 

 

  

Wet loads, more  water 

 

Paddlewheel bushes worn 

 

Check paddlewheel 

collected than indicated 

 

Wheel dirty, flowing over range 

Replace with new paddlewheel, recalibrate 

Dry loads, less water 

 

Requires recalibration test 

 

Set new calibration figure, rear switches 

 collected than indicated 

 

 

 

 

 

 (See calibration guide for details -ME995-7 brochure) 

 

Controller starts counting 

 

Active and contact power 

 

Contactor fused due to excessive current draw from pump 

  when power switched on 

 

  drive short circuited 

 

Relay fused due to excessive current draw on solenoid coil   

 

 

 

 

 

 

 

 

  - install higher current rated contactor or install contactor. 

Controller-  FL(flow), LM(limit), 

Controller malfunction, IC failure 

Replace controller or call for service and advise 

  and or CD(contact drive) LEDs on 

  Diagnostic warning 

 

Sequential fault finding and rectification 

1. 

If  another  ManuFlo  controller  (any  model)  is  available,  simply  unplug  doubtful  unit  and  plug  in  exchange  unit.  If  the  new  unit  is  also  not 
operating correctly, then the problem is isolated to the pulse flowmeter or wiring.

 

2. 

When  checking  flowmeter,  reset  the  ManuFlo  controller.  Remove  the  flow  sensor  and  spin  the  paddlewheel.  Check  that  the  ManuFlo 
controller  has  registered  a  number  of  counts  on  its  display.  If  so,  the  electrical  connections  are  probably  OK.  If  no  counts  are  registered, 
check that 12VDC is supplied to the flow sensor. If supplied, then switch off the ManuFlo controller and replace the RPFS flow sensor. 

 

3. 

The flow sensor paddlewheel is jammed, damaged etc. (For servicing, refer to the flow sensor brochure).

 

 
 
 
 
 
 

System over batch problem 

1. 

Selector  knob  batch  dials  on  ManuFlo    Batch  Controller  may  not  be  positioned  correctly,  and  therefore  not  correspond  to  rotary  switch 
numeric values.

 

2. 

To test, set all numbered dials to the zero position 0000. Then press the RESET toggle. The alarm should beep momentarily - this will 
indicate correct alignment of dials. If alarm does not beep, this indicates incorrect alignment of number dials. To rectify, remove the grey 
colored cap from dial, unscrew knob and pull knob off. Check that the exposed switch shaft’s flat (black) side is horizontal. If not, then turn to 
horizontal and refit the numbered dial knob to the zero number setting. Also check the calibration and pre-act knob settings which are located 
at the rear of the controller

 

3. 

If the Batch Controller is found to be operating correctly, then proceed to checking and testing the flowmeter components.

 

 
 

If in further doubt, contact your local representative, or ManuFlo on ph +61 2 9938 1425 or 9905 4324.

Содержание ManuFlo ME995-7

Страница 1: ...urrent draw Consider wiring an override button N O with spring return for manual batching or top up of water which will be counted by the controller display See wiring diagram C Install the Rota Pulse paddlewheel sensor RPFS P in a straight pipe section with the same diameter pipe as the adaptor tee section with 10x diameter before and 5x diameter after the sensor with no elbows reducers valves or...

Страница 2: ...1 Litre increments up to a maximum 9000 Litres The controller operates from standard 220 260 vac or optional 24vac 110vac or 12 24 VDC voltage supplies Contact output drive is via one or optional two relays or with OC open contact drive to allow control output switching drive of any external voltage Standard controllers are in panel mount form or optionally can be housed in a metal box or IP65 ABS...

Страница 3: ...ected 200L when 190L on LEDs this is 10L more or 5 over 10 190x100 So decrease the calibration value by 5 i e if calibration set to 300 new value is 300 5 300 15 285 Set Calibration U 5 T 8 H 2 4 If the amount collected is less than is shown on the LED display then increase the set calibration value by the same difference e g if collected 180L when 190L on LEDs this is 10L less or 5 under 10 190x1...

Страница 4: ...wo product changeover output drive Allows 2 flowmeter inputs pump drives e g ME995 7 is the standard Batch Controller 240vac powered whereas ME995 7 MC2 is an ME995 7 Batch Controller with a scaled open collector pulse output and a Start Stop Reset PLC commands interface HOUSING ENCLOSURES SHB SHB1 Single enclosure Powder coated metal Single enclosure Powder coated metal Wired with 240vac contacto...

Страница 5: ... N TWIN SHIELDED CABLE at rear of Batch Controller PUMP ME995 WIRING DIAGRAM ACTIVE Optional batch override top up momentary push button switch Standard AC Wiring for Pump and optional Solenoid at rear of Batch Controller ACTIVE Rear ME995 SHIELD 0 v PULSE SHIELDED CABLE CONTACT CONTACT 1 VDC Optionalbatch override top up momentarypush button switch Gate Valve Solenoid Flowmeter VDC 0v Open Contac...

Страница 6: ...tion to larger size pipes is possible depending on pipe wall thickness alternatively the Long Stem LS versions with adaptors are then used With only one moving part and limited intrusion into the pipe and combined with its flow through design the RPFS allows accurate measurement of liquid flows with virtually no head losses Each of the 4 blades of the rotor paddlewheel extends approximately one ce...

Страница 7: ...val of RPFS from Pipe adaptor Fitting Triangular Keyway Type Nipple Adaptor see FIG 6 1 Unscrew the black PVC locking cap anti clockwise 2 Hold the neck of the Tee piece in your left hand grasp the RPFS body with your right hand and turn slowly anti clockwise until the sensor hydraulically raises out of slot then pull upwards out of the socket never by the cable When returning the sensor to nipple...

Страница 8: ...talled in a horizontal inclined or vertical pipe position Note If mounted in horizontal or inclined pipe make sure insertion position of sensor is at top or 45 from top not on the underside Selection of pipe diameter For best results use the table below Pipe size Flowrange Litres min Pulses Litre mm Min Max approx 1 2 20 13 160 116 25 20 250 75 32 30 410 46 40 50 640 30 50 90 1000 20 63 132 1580 1...

Страница 9: ... SC140 LS 150 mm PVC150SC LS SCP150 LS SC160 LS 160 mm SCPE160 LS SC160 LS 200 mm PVC200SC LS SCP200 LS SC200 LS 225 mm SCPE225 LS SC225 LS 250 mm SCP250 LS SC250 LS 280 mm SC280 LS 300 mm PVC300SC LS SCPE300 LS SC315 LS 315 mm SC315 LS 500 mm Galvanised iron threaded ends BSP female 2000 kPa Note 25mm can be supplied with straight pipe sections already fitted Part GAL25 T2 PVC T piece Class 18 Ca...

Страница 10: ...RPFS and ME995 Wiring and Plumbing Diagrams c 2004 Manu Electronics Pty Ltd 1 ...

Страница 11: ...RPFS and ME995 Wiring and Plumbing Diagrams c 2004 Manu Electronics Pty Ltd 2 ...

Страница 12: ...RPFS and ME995 Wiring and Plumbing Diagrams c 2004 Manu Electronics Pty Ltd 3 ...

Страница 13: ... past batch select Faulty solenoid valve not closing service solenoid valve check air pressure or water does not stop properly insufficient air pressure Wet loads more water Paddlewheel bushes worn Check paddlewheel collected than indicated Wheel dirty flowing over range Replace with new paddlewheel recalibrate Dry loads less water Requires recalibration test Set new calibration figure rear switch...

Страница 14: ...c minimum flowrate required If flow drops below 1 5 Litres sec the pulse fail will activate The equation is Pulse fail frequency Hz Pulses Litre x minimum flowrate of pipe diameter in Litres sec The flowrate frequency Hz minimum setting can be adjusted by soldering a capacitor in parallel with the standard capacitor found on the PCB See Table 2 and diagram below for values and location on the PCB ...

Отзывы: