RPFS

 

ROTA PULSE FLOW SENSOR       

(Slip Insertion Paddlewheel) 

  

DATASHEET 

 

        

 

FEATURES 

 

 

± 2.5% accuracy @ velocity range 0.5 to 8.5 m/sec. 

 

± 1   % accuracy over linear range 0.7 to 7.0 m/sec. 

 

Repeatability of ±0.6%. 

 

 

NPN inductive pulse with internal amplification. 

 

Square wave output with short circuit protection.  

 

 

Inductive coil pulse option for low current applications.

 

 

 

High Pressure options to 2000kpa 

 

 

50

C or 120

C temperature models. 

 

 

Simple installation and maintenance. 

 

Large range of pipe adapter fittings in sizes 20 to 110mm. 

(Larger pipe sizes to 500mm using “Long Stem” –LS version) 

 

 

 

Stainless Steel 17-4PH paddlewheel rotor without magnets. 

 

 

Australian made since 1984. 

(Now with new high speed bush option).

 

 

DESCRIPTION 

The Rota Pulse Flow Sensor (RPFS) paddlewheel insertion type flowmeter uses a proven 
principle  of  flow  measurement,  which  is  used  worldwide.  The  RPFS  comes  in  four  model 
variants: 

 

RPFS-P

 for liquids up to   50

C (plug-in cable) 

 

RPFS-H

 for liquids up to 120

C  

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

   RPFS-P 

 

All model variants insert directly into a large range of pipe adapter fittings available in PVC, Galvanized Iron, Brass, Stainless 
Steel or Polypipe materials, covering pipe sizes 20 to 110mm (standard sizes). This makes the RPFS suitable for a wide range of 
liquid flow measurement, monitoring and batching applications. Using the BSPB & BSPSS fittings adaption to larger size pipes is 
possible depending on pipe wall thickness, alternatively the Long Stem (-LS) versions with adaptors are then used. 

 

With only one moving part and limited intrusion into the pipe, and combined with its flow-through design, the RPFS allows 
accurate measurement of liquid flows with virtually no head losses. 

 

Each of the 4 blades of the rotor (paddlewheel) extends approximately one centimetre into the flowing liquid. The RPFS-P sensor 
generates a square wave pulse with the frequency output proportional to flow velocity and proportional to pipe diameter. The 
RPFS-P incorporates internal amplification, allowing pulse transmission up to 1000 metres to the receiver device. The RPFS-P 
model is specially constructed  with a metal shielding jacket making it immune to electrical interference.  

 

Magnets are not used in the RPFS models, thereby eliminating iron particles jamming the rotor. The alloy rotor used also makes 
the RPFS less susceptible to interference from turbulence and particles hitting the rotor, thereby giving superior flow results.

  

 

SPECIFICATIONS 

 

 

Model 

  RPFS-P 

RPFS-H 

 

Supply voltage 

5-30VDC 

5-30VDC 

 

Output signal 

NPN open collector 

NPN open collector 

 

 

50% duty cycle pulse 

50% duty cycle pulse 

 

Current draw @ 5VDC / 24VDC 

2.5mA / 10mA 

2.5mA / 10mA 

 

Max. switching current  

200 Ma (at 24VDC) 

200 mA  (at 24VDC) 

 

Cable length 

5 metres, plug-in cable  2 metres cable 

 

 

3-core (3 wire) 

2-core shielded (3 wire) 

 

Fluid temperature 

50 °C max. 

120 °C max. 

 

Weather rating 

IP67 

IP65 

 

Pressure rating 

200psi 

400psi 

 

Accuracy 

± 2.5% for 0.5 to 8.5 m/s, ±1% for 0.7 to 7.0 m/s, Repeatability ± 0.6% 

For Pipe Sizes 

15 to 110mm standard,  
Larger pipes via BSPB-LS special adaptor or saddle clamps. 

Содержание ManuFlo ME995-7

Страница 1: ...urrent draw Consider wiring an override button N O with spring return for manual batching or top up of water which will be counted by the controller display See wiring diagram C Install the Rota Pulse paddlewheel sensor RPFS P in a straight pipe section with the same diameter pipe as the adaptor tee section with 10x diameter before and 5x diameter after the sensor with no elbows reducers valves or...

Страница 2: ...1 Litre increments up to a maximum 9000 Litres The controller operates from standard 220 260 vac or optional 24vac 110vac or 12 24 VDC voltage supplies Contact output drive is via one or optional two relays or with OC open contact drive to allow control output switching drive of any external voltage Standard controllers are in panel mount form or optionally can be housed in a metal box or IP65 ABS...

Страница 3: ...ected 200L when 190L on LEDs this is 10L more or 5 over 10 190x100 So decrease the calibration value by 5 i e if calibration set to 300 new value is 300 5 300 15 285 Set Calibration U 5 T 8 H 2 4 If the amount collected is less than is shown on the LED display then increase the set calibration value by the same difference e g if collected 180L when 190L on LEDs this is 10L less or 5 under 10 190x1...

Страница 4: ...wo product changeover output drive Allows 2 flowmeter inputs pump drives e g ME995 7 is the standard Batch Controller 240vac powered whereas ME995 7 MC2 is an ME995 7 Batch Controller with a scaled open collector pulse output and a Start Stop Reset PLC commands interface HOUSING ENCLOSURES SHB SHB1 Single enclosure Powder coated metal Single enclosure Powder coated metal Wired with 240vac contacto...

Страница 5: ... N TWIN SHIELDED CABLE at rear of Batch Controller PUMP ME995 WIRING DIAGRAM ACTIVE Optional batch override top up momentary push button switch Standard AC Wiring for Pump and optional Solenoid at rear of Batch Controller ACTIVE Rear ME995 SHIELD 0 v PULSE SHIELDED CABLE CONTACT CONTACT 1 VDC Optionalbatch override top up momentarypush button switch Gate Valve Solenoid Flowmeter VDC 0v Open Contac...

Страница 6: ...tion to larger size pipes is possible depending on pipe wall thickness alternatively the Long Stem LS versions with adaptors are then used With only one moving part and limited intrusion into the pipe and combined with its flow through design the RPFS allows accurate measurement of liquid flows with virtually no head losses Each of the 4 blades of the rotor paddlewheel extends approximately one ce...

Страница 7: ...val of RPFS from Pipe adaptor Fitting Triangular Keyway Type Nipple Adaptor see FIG 6 1 Unscrew the black PVC locking cap anti clockwise 2 Hold the neck of the Tee piece in your left hand grasp the RPFS body with your right hand and turn slowly anti clockwise until the sensor hydraulically raises out of slot then pull upwards out of the socket never by the cable When returning the sensor to nipple...

Страница 8: ...talled in a horizontal inclined or vertical pipe position Note If mounted in horizontal or inclined pipe make sure insertion position of sensor is at top or 45 from top not on the underside Selection of pipe diameter For best results use the table below Pipe size Flowrange Litres min Pulses Litre mm Min Max approx 1 2 20 13 160 116 25 20 250 75 32 30 410 46 40 50 640 30 50 90 1000 20 63 132 1580 1...

Страница 9: ... SC140 LS 150 mm PVC150SC LS SCP150 LS SC160 LS 160 mm SCPE160 LS SC160 LS 200 mm PVC200SC LS SCP200 LS SC200 LS 225 mm SCPE225 LS SC225 LS 250 mm SCP250 LS SC250 LS 280 mm SC280 LS 300 mm PVC300SC LS SCPE300 LS SC315 LS 315 mm SC315 LS 500 mm Galvanised iron threaded ends BSP female 2000 kPa Note 25mm can be supplied with straight pipe sections already fitted Part GAL25 T2 PVC T piece Class 18 Ca...

Страница 10: ...RPFS and ME995 Wiring and Plumbing Diagrams c 2004 Manu Electronics Pty Ltd 1 ...

Страница 11: ...RPFS and ME995 Wiring and Plumbing Diagrams c 2004 Manu Electronics Pty Ltd 2 ...

Страница 12: ...RPFS and ME995 Wiring and Plumbing Diagrams c 2004 Manu Electronics Pty Ltd 3 ...

Страница 13: ... past batch select Faulty solenoid valve not closing service solenoid valve check air pressure or water does not stop properly insufficient air pressure Wet loads more water Paddlewheel bushes worn Check paddlewheel collected than indicated Wheel dirty flowing over range Replace with new paddlewheel recalibrate Dry loads less water Requires recalibration test Set new calibration figure rear switch...

Страница 14: ...c minimum flowrate required If flow drops below 1 5 Litres sec the pulse fail will activate The equation is Pulse fail frequency Hz Pulses Litre x minimum flowrate of pipe diameter in Litres sec The flowrate frequency Hz minimum setting can be adjusted by soldering a capacitor in parallel with the standard capacitor found on the PCB See Table 2 and diagram below for values and location on the PCB ...

Отзывы: