Part Number 80-1505-3 6/11
215
FAN CYCLE CONTROL
FUNCTION
Energizes and de-energizes the condenser fan motor.
The condenser fan motor typically will be on in the
Freeze cycle and off in the Harvest cycle.
The fan cycle control closes on an increase, and
opens on a decrease in discharge pressure.
CHECK PROCEDURE
1. Verify fan motor windings are not open or
grounded, and fan spins freely.
2. Connect manifold gauges to ice machine.
3. Hook voltmeter in parallel across the fan cycle
control, leaving wires attached.
4. Refer to chart below.
Specifications
Cut-In (Close)
Cut-Out (Open)
First Condenser Fan
250 psig ±5
200 psig ±5
Second Condenser Fan
275 psig ±5
225 psig ±5
FCC Setpoint:
Reading Should
Be:
Fan
Should Be:
Above Cut-In
0 Volts
Running
Below Cut-Out
Line Voltage
Off
Содержание SD0672C
Страница 2: ......
Страница 65: ...Part Number 80 1505 3 6 11 65 This Page Intentionally Left Blank ...
Страница 66: ...66 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 79: ...Part Number 80 1505 3 6 11 79 A B C D ...
Страница 81: ...Part Number 80 1505 3 6 11 81 A B C D E I ...
Страница 90: ...90 Part Number 80 1505 3 6 11 A B C D E F G ...
Страница 94: ...94 Part Number 80 1505 3 6 11 A B C E F D G H ...
Страница 97: ...Part Number 80 1505 3 6 11 97 A B C D F G E ...
Страница 100: ...100 Part Number 80 1505 3 6 11 A B C D E F G H ...
Страница 174: ...174 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 198: ...198 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 229: ...Part Number 80 1505 3 6 11 229 SV1406 USING PINCH OFF TOOL ...
Страница 232: ...232 Part Number 80 1505 3 6 11 ...
Страница 238: ...238 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 276: ...276 Part Number 80 1505 3 6 11 S3070C 230V 50HZ 1PH ...
Страница 283: ...Part Number 80 1505 3 6 11 283 CVD3085 380V 50HZ 3PH ...
Страница 296: ...296 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 297: ......