160
Part Number 80-1505-3 6/11
Suction Pressure High Checklist
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
page 151
Discharge Pressure
•
Discharge pressure is too high and is affecting
suction pressure – refer to “Freeze Cycle
Discharge Pressure High Checklist” page 157
Improper Refrigerant Charge
•
Overcharged
•
Wrong type of refrigerant
•
Non-condensable in system
Other
•
Non-Manitowoc components in system
•
Harvest valve leaking
•
TXV flooding (check bulb mounting)
•
Defective compressor
NOTE: Do not limit your diagnosis to only the items
listed in the checklists.
Содержание SD0672C
Страница 2: ......
Страница 65: ...Part Number 80 1505 3 6 11 65 This Page Intentionally Left Blank ...
Страница 66: ...66 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 79: ...Part Number 80 1505 3 6 11 79 A B C D ...
Страница 81: ...Part Number 80 1505 3 6 11 81 A B C D E I ...
Страница 90: ...90 Part Number 80 1505 3 6 11 A B C D E F G ...
Страница 94: ...94 Part Number 80 1505 3 6 11 A B C E F D G H ...
Страница 97: ...Part Number 80 1505 3 6 11 97 A B C D F G E ...
Страница 100: ...100 Part Number 80 1505 3 6 11 A B C D E F G H ...
Страница 174: ...174 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 198: ...198 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 229: ...Part Number 80 1505 3 6 11 229 SV1406 USING PINCH OFF TOOL ...
Страница 232: ...232 Part Number 80 1505 3 6 11 ...
Страница 238: ...238 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 276: ...276 Part Number 80 1505 3 6 11 S3070C 230V 50HZ 1PH ...
Страница 283: ...Part Number 80 1505 3 6 11 283 CVD3085 380V 50HZ 3PH ...
Страница 296: ...296 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Страница 297: ......