Fire damper - FDMR
Page 42
Version 2023-06-15
TPM 140/19
Ø
D
min.
Ø
D+80
max.
Ø
D+220
≥
100
X
4
0
..
.1
1
0
X
≥
100
≥
50
4
0
..
.1
1
0
≥
5
0
≤
3
0
0
2
5
≤ 300
25
≥
5
0
In gypsum wall construction - mineral wool with fire-resistant coating and fire-resistant boards
■
For connection of following duct
EIS 90
1
FDMR
2
Gypsum wall construction
3
Mineral wool board - min. density 140 kg/m
3
(e.g. PROMAPYR-T150, ROCKWOOL HARDROCK / STEPROCK HD)
4
Fire-resistant coating - th. 1 mm (e.g. PROMASTOP-I)
5
Fire-resistant board - min. th. 15 mm, min. density 870 kg/m
3
(e.g. PROMATECT-H)
6
Screw 4x50 mm - screws must be fixed in the wall construction, use steel anchors if necessary
7
Clamp with threaded rod
8
Duct