Page 11
Version 2023-06-15
Fire damper - FDMR
TPM 140/19
■
Design .41 or .51 with actuator and smoke detector ORS
142 K. The voltage can be AC 230 V or 24 V DC. Design .41
with voltage AC 230 V is equipped with communication
and supply device BKN 230-24-MOD and with actuator BF
24-TN (BFL 24-T, BFN 24-T).
■
The smoke detector is activated when smoke spreads in
air duct system. Deactivation of the smoke detector alarm
status is provided by interruption of supply voltage for
min. 2s.
■
Signalisation of damper blade position "OPEN" and
"CLOSE" is provided by two microswitches.
■
The smoke detector is not part of the damper in the case
of dampers in diameters from DN 100 mm to DN 200 mm
(including). The smoke detector is supplied separately.
Design .41 and .51
Design .41 with actuator BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K and with supply device BKN 230-24-MOD
(voltage AC 230 V)
1
2
3
4
5
6
7
1
2
S2
S1
S3
S5
S4
S6
2
3
4
5
6
1
BAT
Tf
Tf
LED
Communication and supply device BKN 230-24-MOD
Nominal voltage
AC 230 V 50/60Hz
Power consumption
3 W (operating position)
Dimensioning
14 VA (including actuator)
Protection Class
II
Degree of protection
IP 40
Ambient temperature
Non-operating temperature
-20°C … +50°C
-40°C … +80°C
Connection - net
- motor
- terminal board
cable 0,9 m with EURO plug type 26
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm²
Design .51 with actuator BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K (voltage 24 V DC)
1
2
S2
S1
S3
S5
S4
S6
24 V DC
2
3
4
5
6
1
BAT
Tf
Tf
LED