Fire damper - FDMR
TPM 140/19
Communication and control device BKS 24-1B
4
7
8
2
10
1
5
9
an insulation
transformer
~
damper position
breakdown
Notice: Relay contacts are drawn
without power
11
b
a
2-conductor wiring
to BKN230-24
Control
on /off
Reset
Test
External buton
optional
be interchanged
6
3
AC
24V
damper position
operation
Reset
Test
open
closed
alarm
failure
Connection through
conection can
not available
, starting with switching AC 24 on or pressing
«Reset/Test» button
possible cause: • short circuit or interruption of 2-conductor wiring
or damper failure (at BKN..) • Power supply AC 230V missing • defective
thermoelectrical starting • smoke detector activated • exceeded operation time
• Fault in system signalled, system check should be
done
Damper (drive) turning into
of breakdown position
Damper (drive) in
Damper (drive) turning into
of operating position
Damper (drive) in
light diodes
contacts
Description
Cause/Course
state
open
closed
alarm
closed
flashing
6
3
6
3
6
7
6
4
6
4
6
3
6
3
6
7
switched
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
open
open
open
open
open
open
flashing
flashing
• damper blocked
Communication and control device BKS 24-1B
Nominal voltage
AC 24 V 50/60Hz
Power consumption
2,5 W (operating position)
Dimensioning
5 VA
Protection Class
III
Degree of protection
IP 30
Ambient temperature
0°C … +50°C
Connection
11-pole connector ZSO-11, it is not part of BKS24-1B,
ZSO-11 is 11-pole screw terminal 11 x 1,5 mm
2
■
BKS 24-1B communication and control device is used for control
and checks of fire dampers with the BF 24-TN-ST (BFL 24-T-ST, BFN
24-T-ST) actuator in conjunction with the BKN 230-24 supply and
communication device.
■
BKS 24-1B receives information about the situation of the fire
damper through BKN 230-24 supply and communication device
and issues controlling commands.
■
The device is intended for building in into the distribution board.
■
Light diodes on the front side of the device signalise the operating
situations of the damper and breakdowns of the whole system.
■
Potentialless auxiliary contacts enable connection to the master
control system (signaling of the damper position, failure reports,
release of the ventilators etc.).
■
While a flashing green LED pilot light signalises damper blade
motion towards the given position, the same pilot light reports
reaching the required position when shining constantly.
■
If the damper blade, with respect to the given time, does not
reach the required position, then a red LED pilot light starts to
flash and at the same time, the failure contact is active.
■
Once the damper blade reaches the given position, this contact is
deactivated.
■
The LED pilot light keeps flashing unless the failure is unblocked
by means of the RESET button.
■
Except for reporting failures, other three auxiliary contacts are
available. Contacts showing operating and failure position of the
damper are active when the damper is in the given position.
Function check can be done by pressing and holding the button
"RESET/TEST" for longer time. While holding the button, the
damper blade rotates in the direction of the failure position. Fault
function is indicated by the LED pilot light.
■
BKS 24-1B can be connected by means of ZSO-11 11 pole
connector for DIN 35 mm panel.
Communication and control device BKS 24-1B and BKS 24-9A