Page 87
Version 2023-06-15
Fire damper - FDMR
TPM 140/19
Hinge plates
2x
Ø
9
M8 t
o M
16
120
80
5
0
4x
Ø
9
M20
100
150
■
If in doubt, always consult an anchor specialist
engineer such as Halfen or Hilti.
1
Threaded rod M8 - M20
2
Nut M8 - M20
3
Washer for M8 - M20
4
Coupling Nut M8 - M20
5
Anchor
6
Hinge plate - min. thickness 10 mm
7
Concrete screw tested for fire resistance R30-R90,
max. Tension up to 0.75 KN (length 35 mm)
Load capacities of threaded rods F [N] at the
required fire resistance 90 minutes
Size
As [mm²]
Weight G [kg]
for 1 piece
for 1 pair
M8
366
22
44
M10
58
35
70
M12
843
52
104
M14
115
70
140
M16
157
96
192
M18
192
117
234
M20
245
150
300
Without anchor
With anchor
Examples of anchoring to the ceiling construction
Follow the instructions of fixing specialist or installation company
With hinge plate and anchors
Screw with internal
thread and hexagon drive
■
The dampers must be suspended using threaded rods and
mounting profiles. Their dimensioning depend on the
weight of the damper.
■
The dampers and the duct must be suspended separately.
■
Following air-conditioning duct must be suspended or
supported so that all load transfer from the following duct
to the damper flanges is absolutely excluded. Adjacent
duct must be suspended or supported, as required by the
duct suppliers.
■
Threaded rods longer than 1,5 m must be protected by
fire insulation.
Mounting to the ceiling wall
V. SUSPENSION SYSTEMS