LDVR Series Direct Vent Gas Fireplace

10007317

FK12

This auxiliary fan system increases the efficiency of the 

circulation of the heating air. 
The FK1 Fan Assembly is a fixed speed fan system and 

does not allow for variable speed control. It does not use 

the speed control unit or the heat sensor used in the FK4 

Kit.

Specifications

115 Volts / 60 Hz / 56 Watts.

Maintenance

The  fan  itself  does  not  require  regular  maintenance, 

however periodic cleaning of the fan and the surrounding 

area is required. 
Check  the  area  under  the  control  door  (lower  louvre 

assembly) and in front of the fan and wipe or vacuum this 

area at least once a month during the operating season.

Installation

The fan assembly is supplied fully wired eliminating the need 

for a licensed electrician to carry out the installation.
1.  Open the lower Louvre assembly. Move the fan & bracket 

assembly around the gas valve and lines to locate the 

unit against the back wall of the  

appliance, resting 

on the base.

.  With the protective cover removed from the self-adhesive 

‘Velcro’ strips apply mild pressure to the fan & bracket 

unit to secure the strips to the metal panels. No further 

securing is required. 

3.  Power to the fan can be supplied by plugging the supplied 

lead into a conveniently located wall socket or by using 

a hard-wired EB-1 receptacle box.

Optional Accessories Available

Fan Kits

FK24 Fan Assembly

This auxiliary fan system increases the efficiency of the 

circulation of the heated air.
The  FK4  fan  kit  allows  variable  speed  control  of  the 

circulation fan and also incorporates a heat sensor in the 

circuit.

Specifications

115 Volt / 60Hz / 56 Watts 

Maintenance

The  fan  itself  does  not  require  regular  maintenance, 

however periodic cleaning of the fan and the surrounding 

area is required.
Check  the  area  under  the  control  door  (lower  louvre 

assembly) and in front of the fan and wipe or vacuum this 

area at least once a month during the operating season.

Installation

The  fan  assembly  and  other  components  are  supplied 

fully wired, eliminating the need for a licensed electrician 

to carry out the installation.
If hard wiring the fan using Method B (following) we strongly 

recommend the use of a licensed electrician.
1.  Open the lower louvre assembly. Move the fan & bracket 

assembly around the gas valve and lines to locate the 

unit onto the screw studs on the back of the fireplace.

.  Install the thermal sensor under the bottom of the of the 

firebox, locating it over the two 10mm studs and secure 

it with nuts.

3.  Locate the fan speed control unit. This can be fitted 

behind the lower louvre assembly as in Figure 56 or 

located remotely in a conveniently located wall mounted 

electrical box. Remote location of the speed control will 

require suitable extension of the component wiring.

4.  The power supply may be connected in two ways:

  Method A

  Route  the  6’  lead  fitted  to  the  unit  to  a  conveniently 

located wall socket.

 

Method B

 (Using EB-1 Receptacle Box)

  The EB-1 receptacle box (Pt. # ZA100) may be hard 

wired into the house supply. The fan lead is then plugged 

into the EB-1 box. For instruction on wiring the EB-1 

receptacle box see the earlier chapter in the Installation 

section of this manual.

FP1230

FK24

fan install

11/02

Thermal 

Sensor

Fan

Fan Speed 

Switch

Gas 

Lines

Valve

EB-1 Recep-

tacle Box

FP130

Fig. 56

  FK4 fan placement.

Содержание 33LDVR

Страница 1: ...from your neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call the fire department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE...

Страница 2: ...enting 11 Venting Information General Venting Information Termination Location 12 General Information Assembling Vent Pipes 13 How to Use the Vent Graph 14 Rear Wall Venting Applications Installation...

Страница 3: ...mbustion air to operate properly 13 This fireplace must not be connected to a chimney flue serving a separate solid fuel burning fireplace 14 When the fireplace is not in use it is recommended that th...

Страница 4: ...exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no lessthanone half 1 2 inchinsize GASVENTDIRECTLY BELOW KEEP CLEAR OF ALL...

Страница 5: ...E 24 632 mm 24 610 mm 27 686 mm 31 788 mm F 11 292 mm 16 406 mm 16 406 mm 16 406 mm G 14 362 mm 18 476 mm 18 476 mm 18 476 mm H 19 501 mm 24 616 mm 24 616 mm 27 686 mm I 23 590 mm 27 705 mm 27 705 mm...

Страница 6: ...nd 3b and the following Mantel Charts The fitting of a bay window trim kit does not effect the distances and reference points referred to in the diagram and chart Noncombustible mantels and legs may b...

Страница 7: ...ges out 90 on both sides of the fireplace Slide the fireplace into the framed opening until the flanges contact the front surfaces of the fram ing Level the unit and secure it firmly in place FP1544 n...

Страница 8: ...e gas control is equipped with a captured screw type pressure test point therefore it is not necessary to provide a 1 8 test point up stream of the control When using copper or flex connector use only...

Страница 9: ...line to the brass screw polarized of the socket assembly 6 Connect the white wire of the power line to the chrome screw of the socket assembly 7 Connect the ground wire of the supply line to the green...

Страница 10: ...e with Synetek electronic control wiring diagram FP1571 Pilot Main AF 4000 White or Green Green or White Orange or White Main Module Black Gnd Brown Brown Black Red SWI SWI Extension Harness FP1866 wi...

Страница 11: ...24 610 mm General Venting There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 610 mm from the front of the termination hood Donotlocatetermination...

Страница 12: ...let 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9...

Страница 13: ...igh Temperature Sealant Hose Clamp FP1471 Fig 13 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustib...

Страница 14: ...s 20 508mm Fig 16 Only one 45 elbow is allowed in these installations Minimum clearances between vent pipe and combus tible materials are as follows Top 2 51 mm Sides 1 25 mm Bottom 1 25 mm Horizontal...

Страница 15: ...0mm 10 264mm Fireplace Hearth Framing Detail Opening for Noncombustible Wall 7 190mm VO584 100 Fig 17 Locate vent opening on wall ZCS101 Zero Clearance Sleeve 3 11 99 djt Max Length 12 305mm 8 Screws...

Страница 16: ...iding It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length The horizontal vent run refers to the total length of vent pipe from the f...

Страница 17: ...han 17 5 2 m The maximum number of 45 elbows permitted per side wall installation is six 6 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the hor...

Страница 18: ...for combustible walls STEP 3 Attach the appropriate venting component s to the in ner and outer flue collars of the fireplace using three 3 screws Fig 29 Follow with the installation of the inner and...

Страница 19: ...allations When it is not possible to meet the required vent terminal clearances of 12 305 mm above grade level a snorkel vent kit 7TDVSNORK is required It allows installation depth of down to 7 178 mm...

Страница 20: ...n approved for 1 Vertical installations up to 40 12 m in height Up to 10 3 m horizontal vent run can be installed within the vent system using a maximum of three 90 elbows Vertical Through the Roof Ap...

Страница 21: ...and seal around the pipe 10 Add additional vent lengths for proper height Fig 40 11 Install vertical vent termination CFM100 Firestop Vertical 09 20 00 11 11 Joist Joist Firestop Spacer Nails 4 Upper...

Страница 22: ...Up Installation 1 26 00 djt 40 12 m Storm Collar Roof Flash ing Vent Termination Roof 2 Min Roof Support Attic Insulation Shield Attic Insulation Joists Joists FP1022 Fig 39 Typical straight up insta...

Страница 23: ...mination Kit Starter Kit Model 7TDVSKV Vertical Venting for 7TDVSKV A order 1 12 to 6 12 roof pitch for 7TDVSKV B order 7 12 to 12 12 roof pitch for 7TDVSKV F order flat roof Starter Kit for Below Gra...

Страница 24: ...eaner within the first few weeks of operation Aftertheinitialcleaningprocesstheglassshouldbecleaned twoorthreetimesduringeachoperatingseasondepending on the environment in the house The use of any non...

Страница 25: ...8 33LDVR 1 Place rear log left A41 on rear bracket ensure the notch on the left end locates against the bend up on the left side of rear bracket 2 Place rear log right A42 on rear bracket ensure the n...

Страница 26: ...on the burner housing as sembly 36LDVR 1 Place rear log B158 on rear bracket ensure log is seated properly to the bracket and located to the two pins so it will not move from side to side and is firml...

Страница 27: ...g using the hole locator under the log and on top of front right log 8 Scatter lava rock material round the firebox base Do not place any of the lava rock material on the burner housing assembly RN RP...

Страница 28: ...es Direct Vent Gas Fireplace 10007317 LG384 33LDV log flames 1 05 Glowing Embers LG384 33LDVR 6 LOG FLAMES Glowing Embers LG482 36LDVR 6 OG FLAMES Glowing Embers LG415 39LDVR Glowing Embers LG435 43LD...

Страница 29: ...area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electri...

Страница 30: ...repair it call a qualified service technician Force or attempting repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified se...

Страница 31: ...you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury and loss of life Lighting Instructions Turning Off the Gas to the Appliance FP297A I...

Страница 32: ...t supplied must be used to conduct this test 3 Pilot burning no gas to A Wall switch or wires Check wall switch and wires for proper connections main burner defective Jumper wire accross terminals at...

Страница 33: ...Continuously Monitored Heating Cycle Complete LED OFF NO YES NO NO YES Abnormal Operation 5 sec Inter Trial Delay LED Steady Flash Lockout Flame detected out of sequence Reset by interrupting ON OFF s...

Страница 34: ...ROUND wire is securely connected to an appropriate metal portion of the valve or pilot assembly A proper ground is essential to spark igniter operation Make certain the pilot flame is in contact with...

Страница 35: ...lot Off On Switch Remote Off Switch Adjustment S Pilot Connection I Pilot Connection FP1762 Figure 50 AF4000 MOD Module Right Side 0 F MODULE END 6 Volt DC Adapter Power Connection 8 Pin IPI Connectio...

Страница 36: ...the fireplace Ensure there is no blockage in the pilot line Sensor Safety Protection for Flame Sensor Error Code 4 beeps every one second Description of Fault Warn users the pilot flame sensor detects...

Страница 37: ...IT regulator conversion 10 03 OF F P I L O T O FC107 SIT820 valve conversion 10 03 A B C OF F P I L O T O FC107 108 T 6 REAR BRACKET Natural Gas Log Locator Pin Propane Gas Log Locator Pin KT615 Fig 5...

Страница 38: ...checked for leaks and the gas supply has been bled 2 After bleeding the gas line and checking for leaks with a soap solution replace the window frame assembly Fire up the unit check for flame impinge...

Страница 39: ...lve Maintenance Most of these components may require only an occasional checkup and cleaning and some may require adjustment If repair is necessary it should be performed by a qualified technician 1 T...

Страница 40: ...iscontinue colors and products at any time without notice 33 36 39 43LDVR HI LO 22 21 19a b 18a b 41 17 30 33LDVR 1 1a 1b 1c 1d 1e 1f 1a 36LDVR 1 1g 1h 1i 2 3 6a b 8 7a b 9 11 12 13 14 15 16 20 23 24...

Страница 41: ...Pilot Hood 10002385 10002385 10002385 10002385 10 Manifold Tubing w Fittings 57318 57318 57318 57318 11 Thermocouple RN RP 53373 53373 53373 53373 12 Thermopile RN RP 51827 51827 51827 51827 13 Elect...

Страница 42: ...n 10008615 10008615 10008615 10008615 43 Clip Pin Hitch 10008616 10008616 10008616 10008616 44 Main Module IN 20011895 20011895 20011895 n a 45 AC Adaptor IN 20011900 20011900 20011900 n a 46 24 Wire...

Страница 43: ...rates a heat sensor in the circuit Specifications 115 Volt 60Hz 56 Watts Maintenance The fan itself does not require regular maintenance however periodic cleaning of the fan and the surrounding area i...

Страница 44: ...24 fan wiring Takecarewhenhandlingtherefractorypanels as they are fragile until held in place and supported Installation Refer to Figures 58 59 1 Remove the front window frame assembly 2 Remove the lo...

Страница 45: ...33LDVR 33DVMTKB Black Adjustable Medium Trim Kit Appliance Model Trim Kit 36LDVR ADVMTKP Polished Brass 36LDVR ADVMTKS Pewter 36LDVR ADVMTKB Black 39LDVR ADVMTKP Polished Brass 39LDVR ADVMTKS Pewter 3...

Страница 46: ...46 LDVR Series Direct Vent Gas Fireplace 10007317...

Страница 47: ...he installation instructions The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and doe...

Страница 48: ...7 5 81 82 58 36LDVRRP 57 5 82 83 58 36LDVREN 63 6 81 82 58 36LDVREP 63 6 82 83 58 36LDVRIN 63 6 81 82 58 36LDVRIP 63 6 82 83 58 39LDVRRN 50 2 76 79 63 39LDVRRP 50 2 79 80 63 39LDVREN 54 2 78 79 63 39L...

Отзывы: