LDVR Series Direct Vent Gas Fireplace
10007317
Do not back fill around snorkel. A clearance
of at least 4” (102mm) must be maintained
between the snorkel and the soil.
BG401
Snorkel
2/10/99 djt
Foundation Recess
Snorkel
Wall Screws
Recess Brackets
Watertight Seal
Around Pipe
Sheet Metal
Screws
BG401
Fig. 34
Snorkel installation, recessed foundation.
BG400
Below grade installation
2/10/99 djt
10/19/99 added standoffs
24" (610mm)
Minimum*
Zero Clearance
Sleeve
(if required)
Firestop
7” Pipe
7TDVSNORK
(Snorkel)
4” (10mm)
Clearance
Min.
Window
Well
Gravel
Drain
Foundation Wall
BG400
Fig. 33
Below grade installation.
*A minimum of 4” (608mm) ver-
tical pipe must be installed when
using 7TDVSNORK Kit.
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first, then secure to snorkel with self drilling
#8 x 1/ sheet metal screws. It will be necessary to extend
vent pipes out as far as protruding wall face. (Fig. 34)
This Gas Fireplace has been approved for:
1. Vertical installations up to 40’ (1 m) in height. Up to
10’ (3 m) horizontal vent run can be installed within the
vent system using a maximum of three 90° elbows.
Vertical Through-the-Roof Applications
CFM148
Maximum
10’
(3 m)
Minimum
8’ (.4 m) /
Maximum
40’ (1 m) Vertical
Rise
CFM148
Pipe Straps Every 3’
(914 mm)
Fig. 35
Support straps for horizontal runs.
This Gas Fireplace has been approved for:
1. Vertical installations up to 40’ (1 m) in height. Up to
10’ (3 m) horizontal vent run can be installed within the
vent system using a maximum of three 90° elbows.
. Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal level
the maximum horizontal length must be reduced by 18”
(457 mm).
Example: Maximum horizontal length
0 x 45° elbows = 10’ (3 m)
1 x 45° elbows = 8
¹⁄₂
’ (.6 m)
x 45° elbows = 7’ (.1 m)
3. A minimum of an 8’ vertical rise.
4. Two sets of 45° elbows offsets within these vertical
installations. From 0 to a maximum of 8’ (.4 m) of vent
pipe can be used between elbows. (Fig. 36)
5. 7DVCS must be used to support offsets. (Fig. 36) This
application will require that you first determine the roof
pitch and use the appropriate 7DVSKV (A, B or F).
(Refer to Venting Components List, Page 3)