Your fireplace is approved to be vented either through the
side wall, or vertically through the roof.
•
Only Vermont Castings Group venting components
specifically approved and labelled for this fireplace may
be used.
•
Vent terminations shall not be recessed into a wall or
siding.
•
Horizontal venting which incorporates the twist lock pipe
must be installed on a level plane without an inclining
or declining slope.
•
Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of 1”
(5 mm) per 4” (610 mm).
General Venting
There must not be any obstruction
such as bushes,
garden sheds, fences, decks or utility buildings within 4”
(610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow or ice
build up may occur. Be sure to check vent termination area
after snow falls, and clear to prevent accidental blockage
of venting system. When using snow blowers, make sure
snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing
the minimum clearances as shown on the next page.
*Check with local codes or in absence of same with
CSAB149.1 Installation Codes (1991) for Canada or follow
the current National Fuel Gas Code, ANSI Z3.1/NFPA
54 for installations in the USA.