If there is no appropriate grounding point on the cabinet, we also can connect the
grounding cable of the router to other grounding bar of the installation place.
Fire hose and lightning rod grounding of the building are not the proper grounding
location; the grounding cable of the device should be connected to the engineering
grounding of the equipment room.
3.3 (Optional) Install SPD
3.3.1 Install AC Power SPD
The AC power SPD (surge protection device) suppresses the transient overvoltage caused by
lightning inductance shock or other reasons on the power transmission line. When a SPD is
used, the AC power first enters the SPD and then enters the device.
Figure 3-17 The power SPD
1.Socket
Connects the router power.
2.Normal work indicator (green)
on: indicates that the circuit is running normally.
Off: indicates that the protection circuit is damaged.
3.Grounding
and
polarity
detection
indicator (red)
on: indicates the wiring error (the PE is not connected or the
live wire and naught wire are reversely connected). At this
time, check the power supply circuit.
4.Power switch
Turn on or turn off the power.
5.Automatic overload protector
If the overload occurs, the power is cut off. When the overload
comes to recovery, the power resets automatically.
6.Standard socket
Connects to the power in the equipment room via the power
cable.
The power SPD is not provided with the router. The user can purchase it as required.