Appendix figure F-1 The diagram of S12800 wiring
The wiring principle is that the interface cables are separate from the power cables. With the
reasonable wiring, you can un-install or install the switch fan module, power module and other
components, improving the efficiency.
The interface cables are bundled to the two sides of the cabinet via the two cabling racks
at the front of the chassis. According to the machine room of the user (the signal cable of
the machine room is connected from the cabling rack at the top of the cabinet, or from the
cabling slot under the ground), arrange the cabling from the top or under the ground.
Arrange all transferred data signal cable connectors at the bottom of the cabinet (It cannot
be placed outside the chassis, which is easy to be touched).
The power cables go from the left side of the cabinet back and arrange the cabling from
the top or under the ground according to the machine room of the user (distribution
cabinet, lightning protection box, terminal block, etc.).
The too long cables can adopt the cable tie to bundle. The cables cannot be bundled to the
outlet of the switch, so as to prevent premature aging of the cable.
The cables are fixed at the nearest location of the switch. The cables between the fixing
point and the switch interface keep loose. To mark the cable, paste the label on it.