48
UK | Commissioning
LEDs
Parameter
Set value /
ventilation level
Setting /
description
EnOcean
0
1
EnOcean module not present
EnOcean module present
Use of the EnOcean extension mod
-
ule (PP45 EO) is released with this
adjuster.
Not assigned
–
–
PPB 30 K
0
1
2
3
No PPB 30 K
1 PPB 30 K
2 PPB 30 K
3 PPB 30 K
State the number of
PPB30 K units
connected to the RS 485 interface
here.
ModBus
settings
1
2
3
RS-485 inactive
ModBus active 9600 baud
ModBus active 19200 baud
This adjuster activates ModBus and
sets the baud rate.
Notice: When the Modbus interface is
active, PPB 30 K or external sensors/
LTs/RLS cannot be connected.
ModBus
address
1
2
3
4
5
6
7
Address 10
Address 11
Address 12
Address 13
Address 14
Address 15
Address 16
The ModBus address is selected
with this adjuster.
LED flashing modes: LED flashing rapidly LED flashing slowly