HORIZONTAL INSTALLATION
EXHAUST VENT TERMINATION SHALL BE AS FOLLOWS:
A MINIMUM OF 4’ FEET/122Omm BELOW, BESIDE AND 1’ FOOT ABOVE ANY DOOR OR WINDOW THAT
OPENS, OR ANY OPENING INTO A BUILDING.
A MINIMUM OF 2’ FEET/610mm FROM ANY ADJACENT BUILDING OR OVERHANG.
A MINIMUM OF 7’ FEET/2130mm ABOVE GRADE, WHEN LOCATED ADJACENT TO PUBLIC WALKWAYS.
A MINIMUM OF 2’ FEET/610mm ABOVE GRASS, PLANTS OR OTHER COMBUSTIBLES.
Note: The pipe lengths shown are for reference only.
Your actual pipe length requirements may differ.
SINGLE WALL PIPE SHALL NOT BE
USED FOR ANY INSTALLATION.
HORIZONTAL INSTALLATION SHALL
BE A MAXIMUM OF 5’ FEET.
WARNING:
Vent surfaces can become hot enough to cause burns
if touched. Non-combustible shielding may be required.
PLEASE FOLLOW THE PELLET VENT MANUFACTURER’S INSTRUCTIONS AND LOCAL BUILDING CODES
FOR THE CLEARANCES TO COMBUSIBLES REQUIRED FOR INSTALLATION OF THE VENT PIPE BEING
USED.
WALL THIMBLE
MIN. 12"
CLEARANCE
RAIN CAP
STOVE ADAPTER
STOVE ADAPTER
MINIMUM 6"
(152mm)
CLEARANCE
12”
(304 mm)
Wall Thimble
Содержание Winchester WINACI
Страница 21: ...21 MAGNUM WIN INSERT INSTALLATION ...
Страница 25: ...25 ...
Страница 26: ...Fireplace Insert Shroud Installation Diagram 26 ...
Страница 27: ...27 Thermostat wire connection Low voltage thermostat Molex Plug 24 volt thermostat hookup ...
Страница 41: ...AC MODEL WIRING DIAGRAM WARNING DISCONNECT POWER BEFORE SERVICING THIS UNIT 41 DHC 3000 AC board ...
Страница 42: ...42 DC MODEL DDC 3000 WIRING DIAGRAM WARNING DISCONNECT POWER BEFORE SERVICING THIS UNIT ...