48
58-640 PULSAR Model R96 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
diagnostic/Condition
Process Variables
Quality
Sub-status
Limit
ADC Failure
All PVs
Bad
Device Failure
Constant limited
EEPROM Error
All PVs
Bad
Device Failure
Constant limited
No Fiducial
All PVs except
Elec Temperature
Bad
Device Failure
Constant limited
Too Many Echoes
All PVs except
Elec Temperature
Bad
Device Failure
Constant limited
Echo Lost
All PVs except
Elec Temperature
Bad
Device Failure
Constant limited
Inferred Level
Echo Strength
Echo Margin
Bad
Device Failure
Constant limited
Default Parameters
ALL PVs
Bad
Config Error
Not limited
MeasType != Volume &
Level
Volume
Bad
Config Error
Constant limited
High Volume Alarm
Volume
Bad
Config Error
High limited
Safety Zone Alarm
Level, Distance, Volume Bad
Non-Specific
Not limited
Initializing
All PVs except
Elec Temperature
Uncertain
Initial Value
Constant limited
Ramp Slope Error
All PVs
Good
Non-specific
Not limited
High Elec Temp
All PVs
Good
Non-specific
Not limited
Low Elec Temp
All PVs
Good
Non-specific
Not limited
Calibration Req’d
All PVs
Good
Non-specific
Not limited
Reject Curve Invalid
All PVs
Good
Non-specific
Not limited
Max Jump Exceeded
All PVs
Good
Non-specific
Not limited
Low Echo Margin
All PVs
Good
Non-specific
Not limited
High Surface Velocity
All PVs
Good
Non-specific
Not limited
TB Config Changed
All PVs
Good
Non-specific
Not limited
Sequence Record
All PVs
Good
Non-specific
Not limited.