: The connection for the PV input from another block.
LO_ALM
: The LO alarm data.
LO_LIM
: The setting for the alarm limit used to detect the
LO alarm condition.
LO_LO_ALM
: The LO _LO alarm data.
LO_LO_LIM
: The setting for the alarm limit used to
detect the LO_LO alarm condition.
LO_LO_PRI
: The priority of the LO_LO alarm.
LO_PRI
: The priority of the LO alarm.
MODE_BLK
: The actual, target, permitted, and normal
modes of the block.
OUT
: The block input value and status.
OUT_HI_LIM
: The maximum output value allowed.
OUT_LO_LIM
: The minimum output value allowed.
OUT_SCALE
: The high and low scale values associated
with OUT.
PV
: The process variable use in block execution.
PV_FTIME
: The time constant of the first order PV filter.
PV_SCALE
: The high and low scale values associated with
PV.
RATE
: The derivative action time constant.
RCAS_IN
: Target setpoint and status that is provided by a
supervisory host.
RCAS_OUT
: Block setpoint and status that is provided to
a supervisory host.
RESET
: The integral action time constant.
ROUT_IN
: Block output that is provided by a supervisory
host.
ROUT_OUT
: Block output that is provided to a superviso-
ry host.
SHED_OPT
: Defines action to be taken on remote control
device timeout.
SP
: The target block setpoint value.
SP_HI_LIM
: The highest SP value allowed.
SP_LO_LIM
: The lowest SP value allowed.
SP_RATE_DN
: Ramp rate for downward SP changes.
SP_RATE_UP
: Ramp rate for upward SP changes.