13
FD_MAINT_PRI
: Specifies the priority of the MAINT
alarm category.
FD_CHECK_PRI
: Specifies the priority of the CHECK
alarm category.
FD_SIMULATE
: Diagnostic conditions can be manually
supplied when simulation is enabled.
FD_RECOMMEN_ACT
: Describes what actions can be
taken to address an active diagnostic condition.
FD_EXTENDED_ACTIVE_1
: For error conditions that
have been selected in the Extended_Map_1 parameter, this
parameter reflects those that have been detected as active.
FD_EXTENDED_MAP_1
: Allows the user finer control
in selecting multiple conditions contributing to a single
condition that may be mapped for the various alarm
categories.
SERIAL_NUMBER
: Manufacturer specific read-only para-
meter that corresponds to “Magnetrol Serial Number” in
the Transducer Block.
SOFTWARE_REV
: Read-only parameter that corresponds
to “Firmware Version” in the Transducer Block.
HARDWARE_REV
: Read-only parameter that corresponds
to “Hardware Version” in the Transducer Block.
COMPATIBILITY_REV
: Read-only parameter that is
optionally used when replacing field devices. The correct
usage of this parameter presumes that the DEV_REV
value of the replaced device is equal or lower that the
COMPATIBILITY_REV value of the replacing device.
2.3
Transducer Block
The two TRANSDUCER blocks (TB) contained within the
PULSAR Model R96 FF transmitter are custom blocks con-
taining parameters that are pertinent to the transmitter itself.
TRANSDUCER Block 1 (used for level only operation)
contains information such as the Configuration, Diagnostics,
Calibration data, output level and Status information.
TRANSDUCER Block 2 contains parameters for volume
measurement configuration.
The read-only parameters and read-write parameters within
the TB are grouped in a useful configuration.
• The read-only parameters report the block status and
operation modes.
• The read-write parameters affect both the operation of
the function block and the transmitter itself.
58-640 PULSAR Model R96 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
NOTE:
The Transducer Block will automatically
be changed to “Out of Service” when
the local interface (keypad) is used to
change a static parameter online. The
Transducer Block must be manually
placed back in service from the Host
System to resume operation.