FD_MAINT_ACTIVE
: For error conditions that have been
selected for the MAINT alarm category, this parameter
reflects those that have been detected as active.
FD_CHECK_ACTIVE
: For error conditions that have
been selected for the CHECK alarm category, this parame-
ter reflects those that have been detected as active.
FD_FAIL_MAP
: Maps conditions to be detected as active
for the FAIL alarm category.
FD_OFFSPEC_MAP
: Maps conditions to be detected as
active for the OFFSPEC alarm category.
FD_MAINT_MAP
: Maps conditions to be detected as
active for the MAINT alarm category.
FD_CHECK_MAP
: Maps conditions to be detected as
active for the CHECK alarm category.
FD_FAIL_MASK
: Used to suppress an alarm from being
broadcast for single or multiple conditions that are active in
the FAIL alarm category.
FD_OFFSPEC_MASK
: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the OFFSPEC alarm category.
FD_MAINT_MASK
: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the MAINT alarm category.
FD_CHECK_MASK
: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the CHECK alarm category.
FD_FAIL_ALM
: Used to broadcast a change in the associ-
ated active conditions, which are not masked, for the FAIL
alarm category.
FD_OFFSPEC_ALM
: Used to broadcast a change in the
associated active conditions, which are not masked, for the
OFFSPEC alarm category.
FD_MAINT_ALM
: Used to broadcast a change in the
associated active conditions, which are not masked, for the
MAINT alarm category.
FD_CHECK_ALM
: Used to broadcast a change in the
associated active conditions, which are not masked, for the
CHECK alarm category.
FD_FAIL_PRI
: Specifies the priority of the FAIL alarm
category.
FD_OFFSPEC_PRI
: Specifies the priority of the OFF-
SPEC alarm category.
58-640 PULSAR Model R96 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual