43
58-640 PULSAR Model R96 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
Refer to the table below for a complete listing of the Model
R96 diagnostic indicators, along with their explanations,
default categories, and recommended remedies.
NOTES:
1) The remedies shown in this table can also be seen on
the transmitter LCD by viewing the present status
screen when the device is in a diagnostic condition.
2) Those indicators showing failure as the default result
in an alarm condition.
5.1.2 diagnostic indication Simulation
The DD and DTM allow for the ability to manipulate
diagnostic indicators mapped to NE-107 alarm categories in
Resource Block. Intended as a means to verify the configu-
ration of the diagnostic parameters and connected equip-
ment, a user can manually change any indicator in the
Resource Block to and from the active state.
5.1.3 diagnostic indicator table
Below is a listing of the Model R96 diagnostic indicators,
showing their priority, explanations and recommended
remedies. (Priority 1 is highest priority.)
Priority
indicator name
default
Category
Explanation
Remedy (Context Sensitive Help)
1
Software Error
Failure
Unrecoverable error occurred in stored
program.
Contact MAGNETROL Technical Support.
2
RAM Error
Failure
RAM (read/write) memory failing.
3
ADC Error
Failure
Analog-to-digital converter failing.
4
EEPROM Error
Failure
Non-volatile parameter storage failing.
5
Analog Board
Error
Failure
Unrecoverable hardware failure.
6
Spare Indicator
11
OK
Reserved for future use.
7
Spare Indicator 1
OK
Reserved for future use.
8
Default
Parameters
Failure
All saved parameters are set to default
values.
Perform complete Device Setup.
9
Spare Indicator 2
OK
Reserved for future use.