58-640 PULSAR Model R96 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
LOW_CUT
: Limit used in square root processing.
PV_FTIME
: Time constant of a single exponential filter for
the PV, in seconds.
FIELD_VAL
: Raw value of the field device in % of PV
range, with a status reflecting the Transducer condition
before signal characterization (L_TYPE) or filtering
(PV_FTIME).
UPDATE_EVT
: This alert is generated by any change to
the static data.
BLOCK_ALM
: The block alarm is used for all configura-
tion, hardware, or system problems in the block.
ALARM_SUM
: The current alert status, unacknowledged
states, unreported states, and disabled states of the alarms
associated with the function block.
ACK_OPTION
: Selection of whether alarms associated
with the function block will be automatically acknowl-
edged.
ALARM_HYS
: Amount the PV must return within the
alarm limits before the alarm condition clears. Alarm hys-
teresis expressed as a percent of the span of the PV.
HI_HI_PRI
: Priority of the high high alarm.
HI_HI_LIM
: The setting for high high alarm in engineer-
ing units.
HI_PRI
: Priority of the high alarm.
HI_LIM
: The setting for high alarm in engineering units
LO_PRI
: Priority of the low alarm.
LO_LIM
: The setting for low alarm in engineering units.
LO_LO_PRI
: Priority of the low low alarm.
LO_LO_LIM
: The setting for low low alarm in engineering
units.
HI_HI_ALM
: The status for high high alarm and its associ-
ated time stamp.
HI_ALM
: Status for high alarm and associated time stamp.
LO_ALM
: Status for low alarm and associated time stamp.
LO_LO_ALM
: The status for low low alarm and its associ-
ated time stamp.