44
58-640 PULSAR Model R96 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
Priority
indicator name
default
Category
Explanation
Remedy
10
Spare Indicator 3
OK
Reserved for future use.
11
No Fiducial
Failure
The fiducial pulse is not located where
expected, or the fiducial amplitude is
not in the expected range.
Increase Fid Gain. Adjust Window to
obtain Fid Ticks of 100-400.
12
Too Many Echoes
Failure
Excessive number of possible echoes
detected.
Check settings:
Dielectric Range
Sensitivity
Polarization Direction
View Echo Curve.
13
Safety Zone Alarm
Failure
Risk of echo loss if liquid rises above
Top Blocking Distance.
Ensure that liquid cannot reach
Blocking Distance.
14
Echo Lost
Failure
No detectable level signal identified
within the configured range.
Check settings:
Dielectric Range
Sensitivity
Tank Height
View Echo Curve.
15
Spare Indicator 4
OK
Reserved for future use.
16
Spare Indicator
12
OK
Reserved for future use.
17
High Volume Alarm
Failure
Volume calculated from Level reading
exceeds capacity of vessel or custom
table.
Check settings:
Vessel Dimensions,
Custom Table entries
18
Spare Indicator 5
OK
Reserved for future use.
19
Initializing
Function
Check
Distance measurement is inaccurate
while internal filters are settling.
Wait for up to 10 seconds.
20
TB Config Changed
Function
Check
A parameter has been modified from the
User Interface.
If desired, reset Config Changed
indicator in ADVANCED CONFIG.
21
Spare Indicator 6
OK
Reserved for future use.
22
Ramp Slope Error
Out of
Spec
Internal signal timing out of limits
causing inaccurate distance
measurement.
Check accuracy of Distance. Replace
transmitter electronics.
23
High Elec Temp
Out of
Spec
Electronics too hot. May compromise
Distance measurement or damage
instrument.
Shield transmitter from heat source or
increase air circulation.
24
Low Elec Temp
Out of
Spec
Electronics too cold. May compromise
Distance measurement or damage
instrument.
Insulate transmitter or locate remotely
in a warmer area.