6 Commissioning
6.1 Procedure
We recommend the following procedure for initial commissioning:
1.
Taking control unit into operation without network cable.
2.
Check DHCP settings.
3.
Switch off control unit.
4.
Connect network cable.
5.
Switch on control unit.
6.
Read IP address via display.
7.
Check connection between host computer and control unit via
"Ping".
8.
Check connection to the web browser via read IP address.
6.2 Corrective
action
Malfunction
Possible cause
Corrective action
The Ethernet module is not plugged in
correctly.
Check plug contacts. Plug in Ethernet
module again.
Firmware update not performed
correctly.
Perform firmware update via the service
module SM01.
Ethernet module is
not recognised.
The Ethernet module is only
supported by the control units MGC-
PRO.
Check label or type sign of the control
unit.
Firewall blocks access
Configure firewall.
Network connection
cannot be established No IP address
Check DHCP settings/servers
Object access error
Object locked
Table 15: Corrective action