Ethernet Module
MGC-PRO MicroDrive
Installation and network connection
3.1.1
Corrective action
Malfunction
Possible cause
Corrective action
Green LED at the
centre is not
permanently lit.
The Ethernet module is only
supported by the control units MGC-
PRO.
Check label or type sign of the control
unit.
The Ethernet module is not plugged in
correctly.
Check plug contacts. Plug in Ethernet
module again.
Green LED at the
centre is not lit.
Firmware update not performed
correctly.
Perform firmware update via the service
module SM01.
Table 3: Corrective action
3.2 Perform
network
connection
Connect the barrier to a suitable network cable in your ethernet
devices. The socket for the network cable is located in the plug-in
module.
NOTICE!
NOTICE!
Property damage from improper network
connection.
The service interface X9 (RJ-45 socket) at the
control unit is used for service purposes. This is not
an Ethernet interface. MAGNETIC assumes no
liability for any damage from improper network
connection.
Therefore:
– Only qualified staff must connect the Ethernet
module with the network.
– Ethernet devices must only be connected to the
Ethernet interface at the Ethernet module.
3.3 Network
Configuration
DHCP is activated by default. The IP address is thus automatically
assigned by the customer's DHCP server. The assigned IP
address can be called via the display of the MGC-PRO control.
If no DHCP server is available, you may deactivate the function via
the parameter "DHCP". The default IP address is then used.
See page 8, chapter 2, IP address.
You can adjust the IP address via the web surface.
Changes to the settings are only assumed after restarting the
control unit.
10
5815,0001EN / Version 00