Ethernet Module
MGC-PRO MicroDrive
TCP/IP Interface
5815,0001EN / Version 00
17
5.1.2
Address table
The following modbus address table permits access to the most
important functions and conditions of the barrier.
For this, the "Function Codes" 0x3 to 0x6 are used.
See page 6, chapter 1.3 "Reference documents".
Address Name
Data
type
Area
Acces
s
Description
0000
BarControl 16Bit
0 … 4
RW
Barrier commands:
0000 – delete commands
0001 – open
0002 – close
0004
1)
– open high priority
0001
Status
32Bit
RO
Barrier status word
0003 Inputs
16Bit
RO Conditions of the inputs of the MGC-PRO
control unit
0004 Outputs
16Bit
RO Conditions of the outputs of the MGC-PRO
control unit
0005
Loop A
16Bit
RO
Status loop A
0006
Loop B
16Bit
RO
Status loop B
0007
Loop C
16Bit
RO
Status loop C
0008
Loop D
16Bit
RO
Status loop D
1) The command "Open high priority" is not self-resetting. This must be explicitly deleted using "0000 – delete
commands".
Table 7: Address table