6
-116
Table 9 V/f Pattern Default Settings for Drive Capacity 0.4~1.5kW for 240V Class (Continued)
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/f Pattern Selection
—
8
9
A
B
C
D
E
F
E1-04
Max. Output Frequency
Hz
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
E1-05
Max. Output Voltage
V
240.0
240.0
240.0
240.0
240.0
240.0
240.0
240.0
E1-06
Base Frequency
Hz
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Mid. Output Frequency A
V
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
E1-08
Mid. Output Voltage A
V
21.8
27.6
21.8
27.6
17.2
17.2
17.2
17.2
E1-09
Min. Output Frequency
Hz
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
E1-10
Mid. Output Voltage
V
12.6
14.9
12.6
17.2
10.3
10.3
10.3
10.3
E1-11
Mid Output Frequency B
Hz
0
0
0
0
0
0
0
0
E1-12
Mid Output Voltage B
V
0
0
0
0
0
0
0
0
E1-13
Base Voltage
V
0
0
0
0
0
0
0
0
For 480V class units, the value is twice that of 240V class units.
Table 10 V/f Pattern Default Settings for Drive Capacity 2.2~45kW for 240V Class
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/f Pattern Selection
—
0
1
2
3
4
5
6
7
E1-04
Max. Output Frequency
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
E1-05
Max. Output Voltage
V
240.0
240.0
240.0
240.0
240.0
240.0
240.0
240.0
E1-06
Base Frequency
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
E1-07
Mid. Output Frequency A
V
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
E1-08
Mid. Output Voltage A
V
16.1
16.1
16.1
16.1
40.2
57.5
40.2
57.5
E1-09
Min. Output Frequency
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
E1-10
Mid. Output Voltage
V
8.0
8.0
8.0
8.0
6.9
8.0
6.9
8.0
E1-11
Mid Output Frequency B
Hz
0
0
0
0
0
0
0
0
E1-12
Mid Output Voltage B
V
0
0
0
0
0
0
0
0
E1-13
Base Voltage
V
0
0
0
0
0
0
0
0
For 480V class units, the value is twice that of 240V class units.