2
C6-02
Carrier Frequency
1
Sets the carrier
frequency to 2 KHz
C6-11
Carrier Frequency for Open Loop
Vector Control
n/a
Not applicable if V/F
control is selected.
D1-01 thru
D1-04
Frequency Reference when using
multi-function inputs
n/a
Frequency reference
comes from operator.
D1-17
Frequency Reference when Jog
Frequency Reference is selected
via multi-function input terminals
n/a
Frequency reference set
to operator input.
E1-01
Input Voltage Setting
Line Voltage in Vrms
divided by two.
Set this parameter to
the nominal phase-to-
phase voltage coming
into the drive divided by
two (Beta prototypes
only).
Example: Vin,nom. =
970 Vrms
set this
parameter to 485 Vrms
E1-03
V/F Pattern Selection
“0” for 50 Hz
Or
“F” for Custom
0 is a pre-set V/F
pattern. If this doesn’t
work well, choose F for
custom.
E1-04
Max. Ouptut Frequency
Set to 50 Hz
Only relevant and
necessary if E1-03 is set
to “F”
E1-05
Max. Output Voltage
Set to rated motor
voltage at 50 Hz
divided by two
Example: Vnom for
motor is 960VAC, enter
“480” into E1-05.
E1-06
Base Frequency
Set to 50 Hz
This is the base
frequency of the motor
being driven.
E1-07
Mid Output Frequency, A
Set to same as E1-09 (3
Hz)
Sets V/F curve to
straight line. Only
relevant and necessary
if E1-03 is set to “F”
E1-08
Mid Output Voltage, A
n/a
Not used if V/F curve is
straight line.
E1-09
Min. Output Frequency, Fmin
Set to 3 Hz
Only relevant and
necessary if E1-03 is set
to “F”
E1-10
Min. Output Voltage, Vmin
Set to: motor rated
voltage times Fmin
divided by the quantity
of 2 * 50 Hz
Example: Vmin =
960V*3Hz/(2*50Hz) =
28.8
enter 29 into E1-
10.
Only relevant and
necessary if E1-03 is set
to “F”