23
/
48
Control
flag area
This memory area enables control by the corresponding operation commands. The data structure is shown below.
Each bit corresponds to a counter module ID.
Offset
Data name
Operation command
0x0000
Update parameter
0x0001
Reset
①②
RES
0x0002
Recall preset
①②
RCL
0x0003
Start
①②
STA
0x0004
Load reference point
①②
L
0x0005
Pause
①②
PAU
0x0006
Latch
①②
LCH
0x0007
Request measurement data
R
0x0008
Update parameter complete
0x0009
Reset complete
0x000A
Recall preset complete
0x000B
Start complete
0x000C
Load reference point complete
0x000D
Transmit
measurement
data
complete
1. About the operations update parameter, reset, recall preset, start, and load reference point
The operation sequence is as follows.
Each has a control flag and a corresponding completion flag. When the PLC turns the control flag ON, the MG80-
SC reads the flag and executes the corresponding operation. When the operation is completed, the completion bit
is written back.
The PLC checks the completion bit and turns off the control flag. The MG80-SC checks the control flag and turns
off the completion flag.
2. The operation sequence for requesting measurement data is the same as above.
For measurement data requests, if any bit is set to ON, the MG80-SC writes the measurement data of all
connected counter modules.
3. When the bit is turned ON for the corresponding hold function (pause or latch),
the hold function is enabled.