M3LU
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-2652-A Rev.2 P. 4 / 9
■
WIRING INSTRUCTIONS
• Applicable wire size
Solid:
0.2 to 2.5 mm
2
(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm
2
Tinning wire ends may cause contact failure and therefore is not recommended.
Ferruled: 0.2 to 1.5 mm
2
(0.55 to 1.35 dia.)
The following Phoenix Contact terminals are recommended:
AI 0,25-8YE 0.2 to 0.25 mm
2
AI 0,34-8TQ 0.25 to 0.34 mm
2
AI 0,5-8WH 0.34 to 0.5 mm
2
AI 0,75-8GY 0.5 to 0.75 mm
2
AI 1,0-8RD 0.75 to 1.0 mm
2
AI 1,5-8BK 1.0 to 1.5 mm
2
• Expose wire conductors by 8 mm (0.31”).
8 mm
8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure
Recommended
ferruled wire
EXTERNAL & INTERNAL VIEWS
8 7 6 5 4 3 2 1
ON
OFF
ON
OFF
4 3 2 1
Configuration DIP SW
10 11 12
7
8
9
4
5
6
1
2
3
Configurator Jack
DOWN Button
UP Button
MODE Button
LED3 (LD3)
LED2 (LD2)
LED1 (LD1)
■
FRONT VIEW
■
SIDE VIEW
SW3
SW2
SW1
JP2
2
1
3
JP2
2
1
3
JP2
2
1
3
*
*
For Voltage Input (V) range, switch the JP2 jumper to the 2 – 3 position.
Normal Position
(other than DC Voltage [V] range)
DC Voltage [V] Range Position
The DIP switch setting is required to select output types before setting a precise output range using the PC configurator
software.