CONFIGURATION MODE & DIP SW SETTINGS

When you program the transmitter module, two 
configuration modes are available: Field Configuration 
using DIP SW / control buttons, and PC Software. (The 
Option B type is for the field configuration only.)
The internal DIP switches are used to configure input and 
output type.  Once the module is configured, precise ranges 
are set up with the front control buttons using a simulator 
connected to the input terminals and a multimeter 
connected to the output terminals as a reference.
The calibrated input and output ranges are stored in the 
internal memory.  The module reads the DIP-switch-
calibrated configuration only once after the power supply is 
turned on.  Set the switches with the power supply removed.
Selectable I/O type and ranges are listed in Table 12 and 13.

 

DIP SW CONFIGURATION MODE

Turn the SW3-8 OFF to enable the DIP SW (Field 
Configuration) mode as shown in Table 1.
See Table 3 through 9 to configure the input and Table 10 
for the output.

 

PC CONFIGURATION MODE

Turn the SW3-8 ON to enable the PC Configuration mode 
as shown in Table 1.  All programmable features can be set 
up on a PC regardless of other DIP SW setting except for: (1) 
JP2 to be switched from 1 – 2 to 2 – 3 for DC voltage input 
(See Notes under Table 3), and (2) the output type must be 
selected with the DIP SW1-1 through SW1-4 (See Table 11).
For detailed information on the PC configuration, refer to 
the M3LUCFG instruction manual.

 

CONFIGURATION MODE (SW3) 

Table 1

MODE

SW3-8

Configuration mode can be 
Confirmed with the front LED.

DIP SW

OFF

PC

ON

 

FRONT CONTROL BUTTON LOCK (SW2) 

Table 2

Table 2 setting is applicable to the firmware ID indicated 
below or higher versions (marking on the product): 
MASTER:2.01/SLAVE:1.05

LOCK

SW2-6

PC Configuration is not dis-
abled when the front control 
button function is locked.

Unlock

OFF

Lock

ON

 

INPUT TYPE (SW3) 

Table 3

INPUT

SW3-7

SW3-6

SW3-5 SW3-4...3-1

DC Current
DC mV
DC Voltage*

1

OFF
OFF
OFF

OFF
OFF

ON

OFF

ON

OFF



Thermocouple
RTD
Potentiometer
Resistance

OFF

ON
ON
ON

ON

OFF
OFF

ON

ON

OFF

ON

OFF

Table 4
Table 5
Table 6

*1.  JP2 position switched from (1 – 2) to (2 – 3) for both DIP 

SW and PC configuration.

 

THERMOCOUPLE TYPE (SW3) 

Table 4

T/C

SW3-4

SW3-3

SW3-2

SW3-1

(PR)
K (CA)
E (CRC)

OFF
OFF
OFF

OFF
OFF
OFF

OFF
OFF

ON

OFF

ON

OFF

J (IC)
T (CC)
B (RH)

OFF
OFF
OFF

OFF

ON
ON

ON

OFF
OFF

ON

OFF

ON

R
S
C (WRe 5-26)

OFF
OFF

ON

ON
ON

OFF

ON
ON

OFF

OFF

ON

OFF

N
U
L
P (Platinel II)

ON
ON
ON
ON

OFF
OFF
OFF

ON

OFF

ON
ON

OFF

ON

OFF

ON

OFF

 

RTD TYPE (SW3) 

Table 5

RTD

SW3-4

SW3-3

SW3-2

SW3-1

Pt 100
Pt 200
Pt 300

OFF
OFF
OFF

OFF
OFF
OFF

OFF
OFF

ON

OFF

ON

OFF

Pt 400
Pt 500
Pt 1000

OFF
OFF
OFF

OFF

ON
ON

ON

OFF
OFF

ON

OFF

ON

Pt 50 Ω
JPt 100
Ni 100

OFF
OFF

ON

ON
ON

OFF

ON
ON

OFF

OFF

ON

OFF

Ni 120
Ni 508.4 Ω
Ni-Fe 604
Cu 10 @ 25°C

ON
ON
ON
ON

OFF
OFF
OFF

ON

OFF

ON
ON

OFF

ON

OFF

ON

OFF

 

POTENTIOMETER (SW3) 

Table 6

RESISTANCE

SW3-4

SW3-3

SW3-2

SW3-1

2500 – 4000 Ω
1200 – 2500 Ω
600 – 1200 Ω

OFF
OFF
OFF

OFF
OFF
OFF

OFF
OFF

ON

OFF

ON

OFF

300 – 600 Ω
150 – 300 Ω
80 – 150 Ω

OFF
OFF
OFF

OFF

ON
ON

ON

OFF
OFF

ON

OFF

ON

 

RTD/RESISTANCE WIRES (SW2) 

Table 7

WIRES

SW2-2

SW2-1

2-wire
3-wire
4-wire

OFF
OFF

ON

OFF

ON
ON

 

COLD JUNCTION COMPENSATION (SW2) 

Table 8

COLD JUNCTION COMP.

SW2-3

Disable

ON

Enable

OFF

 

BURNOUT (SW2) 

Table 9

BURNOUT

SW2-5

SW2-4

No burnout

OFF

OFF

Upscale

OFF

ON

Downscale

ON

ON

Содержание M3LU

Страница 1: ...t must be mounted inside a panel Insert a noise filter for the power source connected to the unit TDK Lambda Noise Filter Model RSAN 2006 or equivalent is recommended The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance The actual installation env...

Страница 2: ... where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from the transmitter body for wiring insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALL...

Страница 3: ...the one connected with the CJC Sensor included in the package The CJC Sensor is secured to the terminal 6 Loosen only the terminal 4 5 and connect the T C extension wires Be aware that the AC power and DC power connect to different terminals AC POWERED TYPE B 1 3 2 4 5 6 CONFIGURATOR JACK 7 8 11 12 3 2 1 POT DC max min 2 wire RTD 3 wire RTD 4 wire RTD A A T C OUTPUT DC POWER B B A B A B VOLT mA mV...

Страница 4: ...0 75 8GY 0 5 to 0 75 mm2 AI 1 0 8RD 0 75 to 1 0 mm2 AI 1 5 8BK 1 0 to 1 5 mm2 Expose wire conductors by 8 mm 0 31 8 mm 8 mm 4 mm dia max 4 mm dia max Wire exposure Recommended ferruled wire EXTERNAL INTERNAL VIEWS 8 7 6 5 4 3 2 1 ON OFF ON OFF 4 3 2 1 Configuration DIP SW 10 11 12 7 8 9 4 5 6 1 2 3 Configurator Jack DOWN Button UP Button MODE Button LED3 LD3 LED2 LD2 LED1 LD1 FRONT VIEW SIDE VIEW ...

Страница 5: ... MODE SW3 8 Configuration mode can be Confirmed with the front LED DIP SW OFF PC ON FRONT CONTROL BUTTON LOCK SW2 Table 2 Table 2 setting is applicable to the firmware ID indicated below or higher versions marking on the product MASTER 2 01 SLAVE 1 05 LOCK SW2 6 PC Configuration is not dis abled when the front control button function is locked Unlock OFF Lock ON INPUT TYPE SW3 Table 3 INPUT SW3 7 ...

Страница 6: ...ator Power Source Example with V mA input See Connection Diagram for other input types Example with DC power INPUT OUTPUT RANGING Example Setting both input and output to 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LU x A or the green LED turns on model M3LU x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1 red LED is ON and the LD2 red ...

Страница 7: ... simulated 100 input signal Adjust simulated input until the output meter shows desired 0 output Adjust simulated input until the output meter shows desired 100 output LD1 LD1 ZERO SPAN ADJUSTMENTS After the transmitter is installed and operational fine zero and span tuning can be performed as explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the green LED is blin...

Страница 8: ...latinel II 20 20 20 20 270 to 1300 200 to 600 200 to 900 0 to 1395 130 to 1300 200 to 600 200 to 900 0 to 1395 0 30 0 20 0 25 0 25 36 36 36 36 454 to 2372 328 to 1112 328 to 1652 32 to 2543 202 to 2372 328 to 1112 328 to 1652 32 to 2543 0 54 0 36 0 45 0 45 RTD C F MIN SPAN MAXIMUM RANGE ACCURACY 1 MIN SPAN MAXIMUM RANGE ACCURACY 1 Pt 100 JIS 97 IEC Pt 200 Pt 300 20 20 20 200 to 850 200 to 850 200 ...

Страница 9: ... ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 11 Burnout in PC Configuration Mode Option A Burnout in DIP SW Configuration Mode PC Configuration RUN Mode Option A The transmitter is configured via PC and is in normal operating conditions DIP SW Configuration RUN Mode The transmitter...

Отзывы: